PRODUCT DATA
95C-10939-11
ML6984, ML7984 Series 4000
Direct Coupled Valve Actuators
FEATURES
Self-contained, motorized globe valve linkage.
Microprocessor-based digital position sensing and
motor control for accurate positioning.
Compact size for easy installation in confined spaces.
NEMA 3R rain-proof cover for outdoor installation.
Self-calibrating for valve stroke from 1/2 in. (13 mm)
to 1 in. (25 mm).
DIP switch input configuration selection.
LED (light-emitting diode) status indication.
Configurable to 3-wire mode for floating models.
710 N 160 lbf (712 N) valve closing force.
Usable with common transformer power supply for
multiple actuators and controllers.
24 Vac or 28 Vdc power supply.
Field-addable position feedback/auxiliary switch
module available for 5-wire models.
APPLICATION
The ML6984 and ML7984 are self-contained, self-
adjusting, motorized valve actuators that mount directly
onto V5011 two-way and V5013 three-way globe valves,
providing linear stem operation between 1/2 in. (13 mm)
and 1 in. (25 mm).
ML6984 is for use with low voltage SPDT Series 20, Series
60 (on-off), or SP3T Series 60 (floating) electro-
mechanical and electronic controllers.
ML7984 is for use with Series 70 0-10 Vdc, 2-10 Vdc, 4-20
mA; electronic Series 90 “SuperMod”; and 135 ohm
modulating controllers.
Contents
Specifications ............................................................................... 2
Ordering Information ................................................................ 2
Installation .................................................................................... 3
Wiring Schematics ..................................................................... 5
Operation ....................................................................................... 9
Replacement Notes .................................................................... 10
Checkout ........................................................................................ 11
Troubleshooting .......................................................................... 12

Questions and Answers

  • T
    Tracy ClementsAug 12, 2025
    What to do if my Honeywell ML6984 motor overheats or smokes?
    • M
      Madison GonzalezAug 12, 2025
      If the Honeywell Controller motor overheats, smokes, or components burn out, this could be due to a failed current sensing circuit or other failed electronic components. Replace the actuator and ensure that: the correct actuator is used, it is properly installed, it is not operated before mounting on the valve supply, and the proper voltage supply is used.
  • S
    Sonia NicholsAug 16, 2025
    How to fix a Honeywell ML6984 valve seat that leaks?
    • E
      Eric ThompsonAug 16, 2025
      If the Honeywell Controller valve seat leaks or won't close properly, it could be due to several reasons. First, the wrong actuator might be in use, or the system head pressure may be too high, so check the valve close-off rating and the voltage at the actuator terminals. Second, the actuator may not be properly installed; ensure the valve stem is fully threaded into the brass drive shaft and locked with the set screw. Finally, incorrect DIP switch settings could be the cause; check them against the Product Instruction Sheet.
  • S
    Savannah WallAug 20, 2025
    Why is the LED on my Honeywell ML6984 off?
    • S
      Sylvia WilliamsonAug 20, 2025
      If the Honeywell Controller's LED is off, it could be due to no or low power supply. Check the voltage on terminals T5 and T6. Alternatively, it could be in error mode due to gearbox damage. In this case, check the power supply and calibration cycle. Also, ensure the valve stroke length is between 1/2 in. and 1-1/4 in. Reset the device by momentarily disconnecting power at T5 and T6.
  • A
    Anthony StewartAug 23, 2025
    Why does the Honeywell Controller actuator yoke corrode?
    • J
      Julie WalkerAug 23, 2025
      If the Honeywell Controller actuator yoke corrodes, it is likely due to a galvanic reaction from dissimilar metals if a stainless steel U-bolt is used with an aluminum yoke. Replace the U-bolt with a galvanized U-bolt and nuts.
  • Z
    zacharyperezAug 27, 2025
    How to fix a noisy Honeywell ML6984 motor?
    • C
      Chris FieldsAug 27, 2025
      A noisy motor in your Honeywell Controller could be due to a bearing failure caused by overheating. Check for excessive temperature and replace the entire actuator. Consider using a high-temperature kit (43196000-001). Another cause could be worn-out brushes. Check for excessive cycling and replace the actuator.
  • Q
    qandersonAug 30, 2025
    What to do if Vdc/mA signal drops when connected to Honeywell ML6984?
    • D
      Destiny YatesAug 31, 2025
      If the Vdc/mA signal drops when connected to the Honeywell Controller, it could be because the ML7984 is in mA mode with voltage input. Change the DIP switch setting. It could also be signal degradation due to incompatible load impedance. Check the output and ML input impedance specifications.
  • E
    ehunterSep 3, 2025
    Why does the Honeywell ML6984 actuator position drift?
    • G
      Glenn AlvarezSep 4, 2025
      If the Honeywell Controller's floating actuator position drifts when used with a building automation system, it could be a mismatch between the actuator resolution (30 steps) and the BAS controller. Consider reading the actual valve position using a 272630D feedback module, rewiring the actuator for 3-wire control, or programming a daily valve reset.
  • C
    christopher38Sep 7, 2025
    What to do if Honeywell ML6984 ML will not respond?
    • D
      Dylan GardnerSep 7, 2025
      If the Honeywell Controller ML will not respond, it could be due to incorrect DIP switch settings (check against the Product Instruction Sheet), no control signal present (check the controller), incorrect wiring connections (check against the Product Instruction Sheet), or an internal time delay (allow at least 1/2 - 1 second for the ML to respond).

Summary

SPECIFICATIONS

Key Specification Areas

Covers operating environment, electrical ratings, and input signal types for actuators.

INSTALLATION

Actuator-to-Valve Assembly

Step-by-step instructions for attaching the actuator drive shaft to the valve stem.

OPERATION

WIRING SCHEMATICS

ML7984 Analog Control Wiring

ML7984 Modulating Control Wiring

ML7984 Electronic Series 90 Wiring

OPERATION DETAILS

ML7984 Calibration & Operation

Describes ML7984 microprocessor response to signals and self-calibration.

REPLACEMENT & CHECKOUT

System Checkout Procedures

Steps for verifying correct installation and operation of ML7984 and ML6984.

TROUBLESHOOTING

Valve Seat Leaks; Noise; Motor Issues

Addresses common problems like valve leaks, noisy motors, and motor burnout.

Actuator Response Issues

Covers troubleshooting for "ML will not respond" and Vdc/mA signal drop issues.

Honeywell ML6984 Specifications

General IconGeneral
BrandHoneywell
ModelML6984
CategoryController
LanguageEnglish