INSTALLATION INSTRUCTIONS
31-00141M-03
https://customer.honeywell.com/en-US/Pages/department.aspx?cat=HonECC%20Catalog&category=Commercial&catpath=1.1
3 Nm Series Spring Return
Direct Coupled Actuators
MS7103, MS7503, MS3103
20
MS7103, MS7503, MS3103 Spring Return Direct Coupled
Actuators (DCA) are used within heating, ventilating, and air-
conditioning (HVAC) systems. They can drive a variety of
quarter-turn, final control elements requiring spring return
fail-safe operation.
Applications include:
Volume control dampers, mounted directly to the drive
shaft or remotely (with the use of accessory hardware).
Quarter-turn rotary valves, such as ball valves mounted
directly to the drive shaft.
Available with cable on all models
Fast test mode
SPECIFICATIONS
Models:
See Table 1.
Device Weight:
1.7lbs (0.78 kg)
Ambient Operating Temperature:
-40° to 150°F (-40° to 65°C)
Shipping and Storage Temperature:
-40° to +150°F (-40° to +65°C)
1
2-10 VDC
2
0(2)-10 VDC, 10-0(2) VDC
Table 1. Models.
Model Number
Control Input /
Output
Description
SPST
Aux
Switches
1/2”
360°
Conduit
Shaft
Adaptor Torque Supply Voltage
Driving/
Holding
(VA)
Drive
(sec)
MS7103A1021 Modulating (1) No Yes
SCSA
27 lb-in
(3Nm)
24 VAC +/-20% @
50/60 Hz class 2
transformer,
24 VDC +20%/-10%
4/2 90
MS7103A2021
Modulating (1),
Feedback
No Yes
MS7103A2221
Modulating (1),
Feedback
Yes Yes
MS7503A2021 Modulating (2),
Floating,
Feedback
No Yes
MS7503A2221 Yes Yes
MS7103A2024
Modulating (1),
Feedback
No No U-Bolt
MS7103A2224 Yes No U-Bolt
MS3103J1023
Sylk BUS
No
Yes U-Bolt
4.5/2 30-180
MS3103J1024 No U-Bolt
MS3103J1221
Yes
Yes SCSA
MS3103J1222 No SCSA
MS3103J1223 Yes U-Bolt
MS3103J1224 No U-Bolt
MS3103J1021
No
Yes SCSA
MS3103J1022 No SCSA
Question and Answer IconNeed help?

Do you have a question about the Honeywell MS3103 Series and is the answer not in the manual?

Honeywell MS3103 Series Specifications

General IconGeneral
ModelMS3103 Series
Housing MaterialPlastic
Temperature Range-20°C to +60°C
Control Signal4-20 mA
Operating Temperature-20°C to +60°C

Summary

SPECIFICATIONS

INSTALLATION

Location, Preparation, and Mounting Orientation

Details where to install, initial prep, and how to orient the actuator.

Shaft Mounting and Control Signal Selection

Explains shaft length, coupling, signal selection, Sylk address, and stroke adjustment.

Mounting Procedures and IP Ratings

Covers general mounting steps, square shafts, and ingress protection ratings.

WIRING

Control Signal Wiring Diagrams

Illustrates wiring for SPDT, Floating, Modulating, and SYLK control signals.

OPERATION

CHECKOUT

Operational Mode Testing Procedures

Guides through testing Modulating, Floating, and Spring Return operations.