PRODUCT DATA
38-00032-01
Global Field Devices
VRN Pressure Independent Control
Valves and Actuators
APPLICATION
The VRN2 two-way pressure independent control valves
maintain constant flow of hot or chilled water with glycol
solutions up to 50% in closed-loop heating, ventilating,
and air conditioning (HVAC Division 23) systems
regardless of head pressure fluctuations above the
minimum specified pressure drop. These valve assemblies
can be used with Honeywell non-spring return or spring
return direct coupled actuators (DCA).
The built-in differential pressure regulator makes fluid
flow through the valve independent of changes in supply
pressure, eliminating “hunting” by the control system,
even at low coil flow. The pressure regulator virtually
eliminates cavitation in the valve, and decouples the
control valve from the effects of piping components such
as reducers and elbows.
Pressure independent control valves are sized to match
design coil flow regardless of coil size. VRN2 valves
eliminate the need to balance the system for proper flow,
and allow chillers to be operated at design temperature
differential for maximum efficiency at every load
condition. When used in a system with variable speed
pump drives, 3-way valves and coil bypass lines are not
required. In new construction, VRN2 valves perform better
than reverse return piping designs without the extra
materials these systems need.
Pressure-independent control requires less flow, enabling
use of smaller piping, pumps, and chillers.
FEATURES
Sizes from 1/2 to 3 in. with internal (female) NPT
connections.
Controls hot or chilled water with up to 50% glycol.
Regulated flow rates available from 1 to 95 gpm.
Differential pressure regulator for constant pressure
drop across valve seat.
Positive pressure, rolling diaphragm regulator design
for flow control accuracy of ±5%.
Equal percentage flow characteristic using patented
flow control ball insert.
Multiple maximum flow rates available per valve size.
Patented ball seals for low operating torque.
Nickel-chrome plated brass or stainless steel trim.
Choice of factory-installed actuation using
Honeywell MVN or MN/MS series direct coupled
actuators: Floating, Modulating (2-10 V), Non-Spring
Return and Spring Return.
Spring return actuators field-configurable for
normally open or normally closed fail-safe position.
Removable, manual operating handle to control
valve during installation or in an event of power
failure.
Upstream Test Port for venting or pressure gauge
attachment.
Three actuator orientations on the valve for cramped
spaces.
Integral snubber eliminates effect of system
pressure fluctuations and entrapped air while
improving flow performance.
Contents
Application ..................................................................................... 1
Features .......................................................................................... 1
Specifications ............................................................................... 2
Ordering Information ................................................................ 2
Typical Specifications ............................................................... 12
Installation .................................................................................... 13
Operation and Checkout .......................................................... 18

Table of Contents

Other manuals for Honeywell MS8105A1030

Question and Answer IconNeed help?

Do you have a question about the Honeywell MS8105A1030 and is the answer not in the manual?

Honeywell MS8105A1030 Specifications

General IconGeneral
BrandHoneywell
ModelMS8105A1030
CategoryController
LanguageEnglish

Summary

Specifications

Valve and Regulator Specifications

Details valve type, size, pressure, temperature, materials, and regulator specs.

Control Valve Short Order Codes

VRN Flow Rate and Pressure Data

VRN Flow Rate and Differential Pressure Table

Correlates flow rates, pressure, and short order codes for VRN valves.

MVN Actuator Details

MVN Actuator Specifications and Features

Technical specifications, features, and application of the MVN actuator.

Non-Spring Return Actuator

Non-Spring Return Actuator Specs and Features

Technical specifications, features, and application of the non-spring return actuator.

Spring Return Actuator

Spring Return Actuator Specs and Features

Technical specifications, features, and application of the spring return actuator.

Application Notes and Specifications

Valve and Actuator Typical Specifications

Details on valve/actuator requirements, torque, and close-off pressure ratings.

Installation

Installation Preparation and Precautions

Steps for preparation, flushing, and precautions before installation.

Mechanical Installation and Flow Direction

Instructions for physical mounting, sealing, and flow direction.

Electrical Installation and Wiring

Wiring for Fail-in-Place Actuators

Wiring diagrams for floating actuators with on/off and floating control.

Actuator Wiring Configurations

MS7505 Actuator Wiring

Operation and Checkout

Product Operation

Service and Repair

Related product manuals