43-TV-25-30 Iss.6 GLO Aug 07 UK 121
Pen Report Syntax
the syntax for the embedded variables is as follows:
[[PRPtttxynn.v]]
ttt is the type of variables required and can be
MAX = Max value
MAT = Time max value was recorded
MIN = Min Value
MIT = Time min value was recorded
AVE = Average Value
TOT = Totaliser value
STM = Start time of the reports set
x is the report set and can be
C = Current working hour, day, week, month
L = Last completed hour, day, week, month
y is the period and can be
H = Hour
D = Day
W = Week
M = Month
nn is the pen number from 1 to 96
e.g. of some embedded variables
[[PRPTOTLM1.v]] Total for last complete month for pen 1
[[PRPMAXCD23.v]] Max so far for current day for pen 23
[[PRPMATCD23.v]] Time max was recorded for current day for P23
[[PRPSTMCD23.v]] Start time of report for current day for pen 23