26 Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Programming Programming
• It suppresses fire sequences and pages that come below it in priority, until an MN reset clears the “MN Active Tone”. 
Summary of Procedures
Following are the steps involved in creating and programming an MN Active Tone.
1. Build the MN Active Tone Audio Sequence. (See below.)
2. Assign Message Priorities. (See page 27.)
3. Create MN Logic Zones. (See page 28.)
4. Add MN Active Tone Logic to PAM Programming. (See page 28.)
Detailed Procedures
 Build the MN Active Tone Audio Sequence
Open the Audio Settings branch of VeriFire Tools DVC programming, and build the MN Active Tone audio sequence on the Message 
Sequences tab. 
NOTE: Fire or OTHER sequences and pages will not be suppressed for MN alarms without the MN Active Tone, properly prioritized in the 
PAM.
Figure 3.14  Creating an MN Active Tone Sequence 
1. Select and expand a sequence in the 
Message Sequences Number column. 
This example uses Sequence 1. Assign 
the sequence an Evac message type.
2. Type “MN Active Tone” in the Label 
field.
3. Select Command File for “Play 
Forever” for Sequence Step 1. 
4. Select Wave File for “Active Tone” for 
Sequence Step 2.
5. Select Command File for “End Play” for 
Sequence Step 3.
6. Press Play Sequence to listen to and 
review the sequence as a test. The 
Play Forever command will play 200 
times as a test, will play forever in a 
non-test situation. Use the audio-player 
buttons to pause and restart playback.
7. Press Save.