EasyManuals Logo

Honeywell Notifier VESDA-E VEA Series User Manual

Honeywell Notifier VESDA-E VEA Series
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
VEA Product Guide — P/N LS10215-000NF-E:A 07/24/2018 9
Button Lockout Options
Button Lockout Options is also not available for the SLC capable VEA. The front panel button does not have any function associated with it.
Commissioning
Once the detector is configured appropriately, ensure that the detector could communicate with the FACP without any faults. Refer to respective
FACP product guides for configuring the detector over the SLC loop.
Disconnect power to the VEA-040-Axx and verify that communication fault is triggered at the FACP.
Once the above is verified, follow the commissioning process described in VEA-040-Axx product guide.
Make copies of the completed commissioning forms and attachments and forward these to:
Appropriate NOTIFIER sales office
Installing contractor
Designer of the system
End user of the system
Troubleshooting
Faults are reported to FACP via SLC interface in SLC enabled detectors. All of the detector faults are mapped to the following categories at the
FACP. Use the Xtralis VSC software to further investigate the following faults:
Sensor fault
Aspirator fault
Communication fault
Configuration fault
Low flow fault
High flow fault
Filter fault – clogged
Low voltage fault
Refer to the troubleshooting section of VEA-040-Axx product guide for additional fault information.
Commissioning Forms
Customer Name
Site Address
Installer (Name & Contact)
Commissioner (Name & Contact)
Commissioning Checks Done (Y/N) Notes
SLC wiring checks
Correct maximum tube length configured
Periodic airflow testing configured
Filter service interval days configured
Filter replacement due date:
Tube names and correct group factors configured
GPI connected and tested (if used)
SLC address set correctly
SLC detector setup on the SLC loop with no errors at the FACP
Communication fault reported to the FACP when the detector power was
removed.
Detector normalized and running without faults
Sampling points tested using Xtralis VSC Sampling
Smoke test done
Smoke type used:
Transport time (TT) tests done
Detector longest even and odd pipes TT
Walk test done and report generated and printed

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier VESDA-E VEA Series and is the answer not in the manual?

Honeywell Notifier VESDA-E VEA Series Specifications

General IconGeneral
BrandHoneywell
ModelNotifier VESDA-E VEA Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals