N200-102-00 1 I56-3947-202
DESCRIPTION
The LT NFXI-ASD Series is part of the Fire Alarm Aspiration
Sensing Technology
®
(FAAST) family. FAAST is an advanced
re detection system for use where early warning and very early
warning are a requirement. The system continuously draws air
from the controlled environment through a series of sampling holes
to monitor the environment for smoke particulate.
The NFXI-ASD is the addressable version of the FAAST LT range,
communicating with the CIE (Fire Panel) via a proprietary loop
protocol. It is available in 3 different models:
NFXI-ASD11 - Has single channel capability with one laser smoke
sensor.
NFXI-ASD12 - Has single channel capability with two laser smoke
sensors in a common chamber for coincidence
detection.
NFXI-ASD22 - Has two channel capability with two laser smoke
sensors in separate chambers. (one sensor for
each channel).
This guide provides information for mounting and basic installation
using the unit’s default factory settings. For more advanced information
please see the FAAST LT Advanced Setup and Control Guide.
SPECIFICATIONS
Electrical Characteristics
Voltage Range: 18.5 - 31.5 VDC
Supply Current: 1 Channel: 170mA (typical); 360mA (max) @
24 VDC 25
o
C (excluding sounders)
2 Channel: 270mA (typical); 570mA (max) @
24 VDC 25
o
C (excluding sounders)
Communication Loop Supply Voltage: 15 – 29 VDC (Loop current ≤
900mA)
Communication Loop Standby Current: @ 24V: 900 µA max. (poll once
every 5s)
Module Isolator Characteristics
Maximum rated switching current
(under short circuit, Is max): 0.9A @ ≤ 29V
Maximum leakage current (IL max)
with the switch open (isolated state): 15mA
Maximum series impedance with
the switch closed (Zc max): 190 m ohm at 15Vdc; 1A
Power Reset: 0.5s
Congurable Input: Activation Time: 2s (min)
Relay Contact Ratings: 2.0 A @ 30 VDC, 0.5A @ 30 VAC
Environmental Ratings
Temperature: -10°C to 55°C
Relative Humidity: 10% to 93% (non-condensing)
IP Rating: 65
Mechanical
Exterior Dimensions: See Figure 1
Wiring: 0.5 mm² to 2 mm² max
Maximum Single Pipe Length: 100m (Classes B & C) 80m (A)
Maximum Branched Pipe Length: 160m (2 x 80m, Class C)
Maximum Number of Holes See Table 1A
Pipe Spec (EN54-20 Compliance): to EN 61386
(Crush 1, Impact 1, Temp 31)
Outside Pipe Diameter: 25mm (nom) or 27mm (nom)
Shipping Weight: 6.5kg (inc sensors)
FIRE ALARM ASPIRATION SENSING TECHNOLOGY
®
QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT
MODELS NFXI-ASD11, NFXI-ASD12, NFXI-ASD22
Figure 1: Dimensions and Knock-Outs
E N G L I S H
PARTS LIST
Description Quantity
FAAST LT unit 1
Mounting bracket 1
3-pin Terminal block 6
4-pin Terminal block 1
2-pin Terminal block 3
47 k-ohm EOL Resistor 2
USB Cable 1
Front Panel Labelling Pack 1
Wiring Diagram Label 1
Installation Kit CD 1
Quick Installation Guide 1
Important Note
Aspirating Smoke Detectors supplied and installed within the
EU must conform to the EU Construction Products Regulation
(CPR) 305/2011 and the related European Product Standard EN
54-20. FAAST LT has been tested and certied to ensure that it
conforms to the necessary Standards, but strict adherence to this
instruction guide is advised to ensure that the installation meets
the requirements of the CPR.
367 mm
135 mm
56 mm
44 mm
403 mm
356 mm
50 mm 50 mm
60 mm
110 mm
I 56- 3947 - 202
Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER NFXI-ASD11 and is the answer not in the manual?

Honeywell NOTIFIER NFXI-ASD11 Specifications

General IconGeneral
ModelNFXI-ASD11
Operating Voltage15 to 32 VDC
Sensor TypePhotoelectric
TechnologyAdvanced Detection Technology
Operating Temperature0°C to 49°C
Humidity Range10% to 93% RH non-condensing
Air Velocity0 to 4000 ft/min
CompatibilityCompatible with NOTIFIER fire alarm control panels
CertificationsUL, FM, CSFM

Summary

Technical Specifications

Electrical Characteristics

Details voltage range, supply current for 1 and 2 channels, and communication loop specifications.

Module Isolator Characteristics

Specifies maximum switching current, leakage current, and series impedance for module isolators.

Pipe Configuration and Installation

Pipe Hole Configuration

Details available pipe holes on the unit and their usage for different FAAST LT models.

Wiring Installation Procedures

Power, Alarm, and Control Connections

Diagram and notes for connecting power, alarm, and control wiring to the unit.

Terminal Block and Relay Information

Switching Inductive Loads Warning

Critical warning about protecting relay contacts from surges caused by inductive loads.

Setting Device Addresses

Sensor Address Configuration

How to set addresses for smoke sensing devices using rotary decade switches.

Module Address Configuration

How to set the module address using rotary switches located behind the unit door.

Powering Up the Unit

Front Panel Controls and Indicators

Front Panel Indicators and Faults

Detailed descriptions of front panel indicators, their actions, and associated trouble codes.

Front Panel Button Operations

Service and Maintenance

Related product manuals