N200-102-00 4 I56-3947-202  
WIRING INSTALLATION
Power, Alarm and Control Connections
Figure 9: Inside the Detector
CHANNEL 2 FILTER
POWER AND 
ALARM 
CONNECTIONS
CHANNEL 1 FILTER
USB PORT
SENSOR      COVER
POSITION FOR
TEST MAGNET
MODULE MOUNT
Exhaust Pipe
SAMPLING AREA
SAMPLING AREA
1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18
5 6
EARTH BAR
MOUNT
EARTH BAR
MOUNT
F-LT-EB
EARTH BAR
(OPTIONAL)
Note 1: All wiring should comply with local 
requirements and regulations. 
Note 2: Loop wiring must observe the 
recommendations of the panel manufacturer
1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18
3 4
Whenever the FAAST LT is installed outside the risk area, return of 
the exhaust air back into the protected area can reduce ow faults 
due to pressure difference.
!
PLACE 
WIRING 
LABEL 
HERE
If the FAAST LT door is closed for a long time 
(especially  at  high  temperatures)  it  may  be 
necessary  to  use  a  at-bladed  screwdriver 
between the two tabs at the top of the unit to 
lever open the door (as shown above).
MODULE MOUNT
F-LT-PMB 
MODULE MOUNT 
KIT (OPTIONAL)*
*If required, an input/output module 
can be installed into the FAAST LT 
unit. The optional module mount kit 
(F-LT-PMB) will be needed for this.