RELAY MODULES WITH VALVE PROVING
32-00142—01 12
Fig. 7. Typical wiring subbase and sequence for RM7840G with Valve Proving enabled.
RM7840G
POWER
OPERATING
CONTROLS
AND
INTERLOCKS
BURNER
FLAME
SIGNAL
FIRING
RATE
MOTOR
INITIATE
(INITIAL
POWERUP
ONLY)
POWER
STANDBY
PREPURGE
HOLD
DRIVE TO
LOW FIRE
POWER
PILOT
FLAME
MAIN
POWER
PFEP
10 SEC.
(4 SEC. IF
JR1
CLIPPED
PILOT
FLAME
MAIN
POWER
MFEP
PILOT
FLAME
MAIN
RUN
POWER
POSTPURGE
POWER
STANDBY
00 00 10 25 00 1520
MOTOR ACTION
BURNER/BLOWER MOTOR
IGN.
LIMITS AND BURNER CONTROLLER CLOSED
RUNNING INTERLOCKS CLOSED
PREIGNITION INTERLOCK CLOSED
LOW FIRE SW.
SAFE START CHECK
FLAME PROVING
10 SEC. IGN./PILOT
8
10
5
5 SEC.
21
17
TO
7
20TO
5
18
TO
13 15
TO
13 12
TO
M24096B
INTERLOCK. CHECK
13 14
TO
13 14
TO
4
L1
MAIN VALVE 1
9
TIMED
PREPURGE
POWER
FLAME
MAIN
PILOT
ALARM
POWER
FLAME
MAIN
PILOT
ALARMALARMALARMALARM
00
IC
PII
SSC
LED
DISPLAY
RM7840G SWITCHING
MAIN VALVE 2
1
1 2
2
JR3 REMOVED FOR PILOT SEQUENCE MV2 IS MAIN VALVE CLOSEST TO THE BURNER