RELAY MODULES WITH VALVE PROVING
32-00142—01 2
SPECIFICATIONS
Electrical Ratings, see Table 3:
Voltage and Frequency:
RM78xx—120 Vac (+10/-15%), 50 or 60 Hz (±10%).
EC78xx—220–240 Vac (+10/-15%), 50 or 60 Hz
(±10%).
Power Dissipation: RM7800/RM7840/EC7840L: 10W
maximum in the Run mode.
Maximum Total Connected Load: 2000 VA.
Fusing: 15A maximum, Type SC or equivalent Fast Blow.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to +140°F (-40°C to +60°C).
Storage: -40°F to +150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous, noncon-
densing.
Vibration: 0.5G environment.
SIL 3 Capable:
RM7800/RM7840E, G, L, M are SIL 3 Capable in a prop-
erly designed Safety Instrumented system. See
http://www.exida.com/SAEL/Honeywell_7800 for
Certificate Agreement.
Approvals: RM7800L/40G,L:
Underwriters Laboratories Inc. Listed: File No. MP268,
Guide No. MCCZ.
Factory Mutual Approved: Report No. 1V9A0.AF.
Swiss Re (formerly IRI): Acceptable.
Federal Communications Commission, Part 15, Class B—
Emissions.
Approvals: EC7840L:
Factory Mutual Approved: Report No. is still not known.
Swiss Re (formerly IRI): Acceptable.
Federal Communications Commission, Part 15, Class B—
Emissions.
This document provides installation and static checkout
instructions. Other applicable publications are:
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and
marked on the product to make sure the product is
suitable for the application.
3. Installer must be a trained, experienced, flame
safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury,
or death.
To prevent possible hazardous burner operation,
verify safety requirements each time a control is
installed on a burner.
WARNING
Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect the power supply before beginning
installation. More than one power supply
disconnect may be required.
Publication
No. Product
65-0084 Q7800A,B 22-Terminal Wiring Subbase
Product Data
65-0288 S7800A1142 Keyboard Display Module
Product Data
65-0091 S7810A Data ControlBus™ Module
Product Data
65-0095 S7820 Remote Reset Module Product
Data
65-0097 221729C Dust Cover Installation
Instructions
65-0101 S7830 Expanded Annunciator Product
Data
65-0109 R7824, R7847, R7848, R7849, R7851,
R7852, R7861, R7886 Flame Amplifiers
for the 7800 SERIES Product Data
65-0131 221818A Extension Cable Assembly
Product Data
65-0229 7800 SERIES Relay Modules Checkout
and Troubleshooting Product Data
65-0249 S7810M ModBus Module

Other manuals for Honeywell RM7800L1087

Related product manuals