45 65-0315—02
Auxiliary
pump control
Auto
On
16 19
Auxiliary
pump is on
when
CH pump is ON
Slave command
Auxiliary
pump output
Pump A
Pump B
Pump C
None
Boiler pump
control
Auto
On
Boiler pump
output
Pump A
Pump B
Pump C
None
Boiler pump
overrun time
0-600 seconds
0 = Not configured
CH pump
control
Auto
On
CH pump
output
Pump A
Pump B
Pump C
None
CH pump
overrun time
0-600 seconds
0 = Not configured
System
pump control
Auto
On
System
pump output
Pump A
Pump B
Pump C
None
System
pump ourrun
time
0-600 seconds
0 = Not configured
Pump
exercise time
0-600 seconds
0= Not configured
Auxiliary
pump cycles
0-999,999 17 20
Boiler pump
cycles
0-999,999
Burner cycles 0-999,999
Burner run
time
0-999,999
CH pump
cycles
0-999,999
DHW pump
cycles
0-999,999
System
pump cycles
0-999,999
Auxiliary 2
pump cycles
0-999,999
Table 60. Configurable Parameters. (Continued)
Parameter Comment
Table
#
Page
#
DHW high
limit
Enabled
Disabled
18 20
DHW high
limit
response
Suspend DHW
Recycle & hold
Lockout
DHW high
limit setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
Outlet high
limit
response
Recycle & hold
Lockout
Outlet high
limit setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
Stack limit Enabled
Disabled
19 20
Stack limit
delay
0-600 seconds
Stack limit
response
Lockout
Recycle & delay
Stack limit
setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
Delta T
enable
Enabled
Disabled
20 21
Delta T
degrees
-40 °F to 266 °F
(-40 °C to 130 °C)
Delta T delay 0-600 seconds
Delta T
response
Recycle & delay
Lockout
Delta T retry
limit
Delta T rate
limit enable
Enabled
Disabled
Delta T
inverse limit
time
___hour ___min ___sec
Delta T
inverse limit
response
Recycle & delay
Recycle & delay with retry limit
Lockout
Outlet T-rise
enable
Enabled
Disabled
21 21
Heat
exchanger T-
rise enable
Enabled
Disabled
T-rise
degrees
0 °F to 234 °F
(-17 °C to 112 °C)
T-rise
response
Recycle & delay
Recycle & delay with retry limit
Lockout
T-rise retry
limit
0 to 100
T-rise delay ___hour ___min ___sec
Table 60. Configurable Parameters. (Continued)
Parameter Comment
Table
#
Page
#