S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
65-0321—01 60
1
DC2500-CE-200R-200-00000-00-0
2
DC3200-CE-200R-210-10000-00-0
3
Low Fire Hold alarm uses setpoint 1 of alarm 2. If this alarm setpoint is disabled (A2S1TY is NONE), then this alarm is disabled.
Controller
Model (see
footnote)
12121212
Algorithm:
CTRALG
PIDA PIDA PIDA PIDA PIDA PIDA PIDA PIDA
TIMER
DIS DIS DIS DIS DIS DIS DIS DIS
Output:
OUTALG
CURRENT CURRENT CURRENT CURRENT CURRENT CURRENT CURRENT CURRENT
Input 1:
IN1TYP
4–20 mA 4–20 mA 4–20 mA 4–20 mA 4–20 mA 4–20 mA 4–20 mA 4–20 mA
IN1 HI
15 15 150 150 300 300 750 750
IN1 LO
00000000
Input 2:
IN2TYP
DIS (Disable) DIS DIS DIS DIS DIS DIS DIS
Control:
LSP’S
1 ONLY 1 ONLY 1 ONLY 1 ONLY 1 ONLY 1 ONLY 1 ONLY 1 ONLY
SP TRK
NONE NONE NONE NONE NONE NONE NONE NONE
PWR UP
ALSP ALSP ALSP ALSP ALSP ALSP ALSP ALSP
SP Hi
15 15 150 150 300 300 750 750
SP Lo
00000000
ACTION
REVERSE REVERSE REVERSE REVERSE REVERSE REVERSE REVERSE REVERSE
HYST
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Options:
AUXOUT
NONE NONE NONE NONE NONE NONE NONE NONE
DIGIN1
NONE ToAout NONE ToAout NONE ToAout NONE ToAout
DIGIN2
NONE NONE NONE NONE NONE NONE NONE NONE
Communications:
ComADR
30 30 30 30 30 30 30 30
ComSTA
MODB MODB MODB MODB MODB MODB MODB MODB
BAUD
19.2K 19.2K 19.2K 19.2K 19.2K 19.2K 19.2K 19.2K
TX_DLY
11111111
WS FLT
FP BFP BFP BFP BFP BFP BFP BFP B
SDENAB
DIS DIS DIS DIS DIS DIS DIS DIS
UNITS
ENG ENG ENG ENG ENG ENG ENG ENG
LOOPBK
DIS DIS DIS DIS DIS DIS DIS DIS
Alarms:
A1S1TY
PV PV PV PV PV PV PV PV
A1S1VA
15 15 150 150 300 300 750 750
A1S1HL
HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH
A1S2TY
NONE NONE NONE NONE NONE NONE NONE NONE
A2S1TY
NONE
PV
3
NONE
PV
3
NONE
PV
3
NONE
PV
3
A2S1VA
NONE 0 NONE 0 NONE 0 NONE 0
A2S1HL
NONE LOW NONE LOW NONE LOW NONE LOW
A2S2TY
NONE NONE NONE NONE NONE NONE NONE NONE
ALHYST
00000000
ALARM1
NoLATCH NoLATCH NoLATCH NoLATCH NoLATCH NoLATCH NoLATCH NoLATCH
BLOCK
DIS DIS DIS DIS DIS DIS DIS DIS
DIA AL
DIS DIS DIS DIS DIS DIS DIS DIS
Display:
DECMAL
ONE ONE ONE ONE ONE ONE ONE ONE
TUNITS
FFFFFFFF