S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
65-0321—01 62
1
DC2500-CE-200R-200-00000-00-0
2
DC3200-CE-200R-210-10000-00-0
3
Low Fire Hold alarm uses setpoint 1 of alarm 2. If this alarm setpoint is disabled (A2S1TY is NONE), then this alarm is disabled.
Algorithm:
CTRALG
PIDA PIDA PIDA PIDA
TIMER
DIS DIS DIS DIS
Output:
OUTALG
CURRENT CURRENT CURRENT CURRENT
Input 1:
IN1TYP
100H 100H 100H 100H
IN1 HI
1200 1200 1200 1200
IN1 LO
-300 -300 -300 -300
Input 2:
IN2TYP
DIS DIS DIS DIS
Control:
LSP’S
1 ONLY 1 ONLY 1 ONLY 1 ONLY
SP TRK
NONE NONE NONE NONE
PWR UP
ALSP ALSP ALSP ALSP
SP Hi
300 300 500 500
SP Lo
0000
ACTION
REV REV REV REV
Options:
AUXOUT
DIS DIS DIS DIS
DIGIN1
NONE NONE NONE NONE
DIGIN2
NONE NONE NONE NONE
Communications:
ComADR
20 20 20 20
ComSTA
MODB MODB MODB MODB
BAUD
19.2K 19.2K 19.2K 19.2K
TX_DLY
1111
WS FLT
FP BFP BFP BFP B
SDENAB
DIS DIS DIS DIS
UNITS
ENG ENG ENG ENG
Alarms:
A1S1TY
PROC PROC PROC PROC
A1S1VA
300 300 500 500
A1S1HL
HIGH HIGH HIGH HIGH
A1S2TY
NONE NONE NONE NONE
A2S1TY
NONE
PROC
3
NONE
PROC
3
A2S1VA
NONE 50 NONE 50
A2S1HL
NONE LOW NONE LOW
A2S2TY
NONE NONE NONE NONE
ALHYST
0000
ALARM1
NoLATCH NoLATCH NoLATCH NoLATCH
BLOCK
DIS DIS DIS DIS
DIA AL
DIS DIS DIS DIS
Display:
DECMAL
ONE ONE ONE ONE
TUNITS
FFFF