EasyManua.ls Logo

Honeywell S7999D1048 - System Modes and Configuration

Honeywell S7999D1048
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
65-0321—01 8
Fig. 5. Example wiring diagram for one or more boiler
systems with UDC Controller.
Manual assignment of the UDC controllers to their associated
burner/boiler system is required to allow UDC controllers on
the S7810 Modbus™ network. No automatic assignment is
possible.
Careful Modbus™ addressing is required when inserting UDC
controllers in this configuration since duplicate addresses
aren't allowed. Default Modbus™ addresses for the UDC
controllers may need to be changed for them to work properly
in the network.
SYSTEM MODE
S7999D manages a series of (up to 99) local systems in a
S7999D Modbus™ network (see Fig. 8). In the System
configuration, Modbus™ addresses of the nodes are learned
by the System S7999D, so manual assignment isn’t necessary.
Be sure not to duplicate Modbus™ addresses in the nodes.
UP TO A TOTAL OF 99 S7810M AND UDC CONTROLLERS CAN BE CONNECTED TO
THE S7999D. SEE 65-0249 AND UDC MANUALS FOR WIRING.
M33556
CONTROLINKS
CONTROLLER
R7999
A B C
A B C A B C COM POWER
S7999D OI DISPLAY
3
1
“C” TERMINALS ARE CONNECTED INTERNALLY TO 24 VAC “COM”.
3
4
MODBUS BAUD RATE MUST BE SET FOR EITHER 9600 0R 19200 BAUD RATE.
5
SEE 65-0238 FOR R7999 WIRING.
6
120 Ω, 1/4 WATT RESISTOR BETWEEN TERMINALS A AND B OF THE MODBUS AT
THE FARTHEST S7810M MAY BE NECESSARY FOR LONG RS-485 RUNS.
7
CONNECT SHIELD TO EARTH GROUND.
1
SEE 65-0249 FOR CONTROL BUS (LOCAL RS-485 COMMUNICATION BUS) WIRING.
2
1
COM 1
COM 2
24 VAC
3
S7810M
MODBUS
MODULE
B
A
C
8
7
6
2
4
UDC
CONTROLLER
D-
D+
SHLD
16
17
18
5 7

Related product manuals