EasyManua.ls Logo

Honeywell Silent Knight SK-Duct User Manual

Honeywell Silent Knight SK-Duct
6 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Table of Contents Page
[1] Limitations of Duct Smoke Detectors .........................1
[2] General Description .....................................1
[3] Contents of the Duct Smoke Detector Kit ......................1
[4] Detector Installation .....................................1
[5] Sampling Tube Installation ................................2
[6] Measurement Tests ......................................3
[7] Field Wiring ...........................................3
[8] Verification of Operation ..................................4
[9] Detector Cleaning Procedures ..............................4
[10] Sensor Replacement ....................................5
[11] Optional Accessories ....................................5
Warranty .............................................6
BEFORE INSTALLING
Read System Sensor's Applications Guide: Duct Smoke Detectors (HVAG53),
which provides detailed information on detector spacing, placement, zoning,
wiring, and special applications. Copies of this manual are available online
at www.systemsensor.com. NFPA Standards 72 and 90A should also be refer-
enced for detailed information.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following
NFPA 72 requirements. The detector must be tested an maintained regularly fol-
lowing NFPA 72 requirements. According to NFPA, the detector should be visu-
ally inspected semiannually and functionally tested at least once a year. This
may need to be more frequent depending on the air quality of the duct supply air.
[1] LIMITATIONS OF DUCT SMOKE DETECTORS
WARNING
The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR
PROTECTION as a means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user
read NFPA Standards 90A, 72, and 101. The SK-Duct Air Duct Smoke Detectors
are listed per UL 268A.
This device will not operate without electrical power. Fire situations may
cause an interruption of power. The system safeguards should be discussed
with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating
and the cover is installed.
For this detector to function properly, it MUST be installed according to the
instructions in this manual. Furthermore, the detector MUST be operated within
ALL electrical and environmental specifications listed in this manual and the
sensor head installation manual. Failure to comply with these requirements may
prevent the detector from activating when smoke is present in the air duct.
[2] GENERAL DESCRIPTION
Smoke introduced into this air duct system will be distributed throughout the
entire building. Smoke detectors designed for use in air duct systems are used
to sense the presence of smoke in the duct.
Model SK-Duct Air Duct Smoke Detector utilizes photoelectric technology for
the detection of smoke. This detection method, when combined with an ef-
ficient housing design, samples air passing through the duct and allows detec-
tion of a developing hazardous condition. When sufficient smoke is sensed,
an alarm signal is initiated at the fire control panel monitoring the detector,
and appropriate action can be taken to shut off fans, blowers, change over air
handling systems, etc. These actions can facilitate the management of toxic
smoke and fire gases throughout the areas served by the duct system.
The SK-Duct incorporates a sensor cover tamper feature that provides a trou-
ble signal at the panel immediately if the cover is removed or improperly in-
stalled. Proper installation of the sensor cover removes the trouble condition.
If programmed with the system control panel, two LEDs on each duct smoke
detector light to provide local visible indication.
The SK-Duct provides a remote alarm output for use with auxiliary devices,
such as the RA400Z/RA100Z remote LED annunciator, as well as remote test
capability with the RTS451/RTS151 or RTS451KEY/RTS151KEY Remote Test
Stations.
[2.1] DETECTOR FEATURE SET
– Utilizes plug-in head, part number SK-PHOTOR
– Sampling tubes install from front and rear
– Compatible with existing accessories
– Able to address detector per code switches on sensor head.
[3] CONTENTS OF THE DUCT SMOKE DETECTOR KIT
1. Sensor/power board assembly and covers sensor head is factory installed
2. Three #10 sheet metal screws for mounting
3. Drilling template
4. One sampling tube end cap
5. One plastic exhaust tube
NOTE: A sampling tube must be ordered to complete the installation. It must
be the correct length for the width of the duct where it will be installed. See
Table 1 on page 3 to determine the inlet tube required for different duct widths.
[4] DETECTOR INSTALLATION
[4.1] VERIFY DUCT AIR FLOW DIRECTION AND VELOCITY
Model SK-Duct detectors are designed to be used in air handling systems hav-
ing air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to
12 feet can be accommodated. Be sure to check engineering specifications to
ensure that the air velocity in the duct falls within these parameters. If neces-
sary, use a velocity meter (anemometer) to check the air velocity in the duct.
SPECIFICATIONS
Operating Temperature: –4° to 158°F (–20° to 70°C)
32° to 120°F (0° to 49°C) with module installed in the SK-Duct
Storage Temperature: –22° to 158°F (–30° to 70°C)
Humidity: 0% to 93% Relative Humidity Non-condensing
Air Velocity: 100 to 4000 ft./min. (0.5 to 20.3 m/sec.)
Rectangular Footprint Dimensions: 14.38 in L×5 in W×2.5 in D (37 cm L×12.7 cm W×6.36 cm D)
Square Footprint Dimensions: 7.75 in L×9 in W×2.5 in D (19.7 cm L×22.9 cm W×6.35 cm D)
Weight: 1.8 pounds; 0.82 kg
Operating Voltage Range: 15 to 32 VDC
Standby Current: 300 µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)
Max. Alarm Current (LED on): 6.5 mA @ 24 VDC
ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE STANDBY ALARM
RA400Z/RA100Z 0 mA 12 mA Max.
RTS451/RTS151 0 mA 12 mA Max.
RTS451KEY/
RTS151KEY
12 mA 12 mA Max.
NOTE: The SK-Duct comes with the sensor head factory installed, part number SK-PHOTOR.
I56-3432-006
INSTALLATION AND MAINTENANCE INSTRUCTIONS
12 Clintonville Road, Northford, CT 06472-1610
Phone: 203-484-7161 Fax: 203-484-7118
www.silentknight.com
SK-Duct
Air Duct Smoke Detector
1 I56-3432-006
04-12
Question and Answer IconNeed help?

Do you have a question about the Honeywell Silent Knight SK-Duct and is the answer not in the manual?

Honeywell Silent Knight SK-Duct Specifications

General IconGeneral
BrandHoneywell
ModelSilent Knight SK-Duct
CategorySmoke Alarm
LanguageEnglish

Summary

SK-Duct Air Duct Smoke Detector Overview

Specifications

Details operating temperature, humidity, air velocity, and current loads for the detector.

General Description

Explains the detector's photoelectric technology and its function in sensing smoke.

Detector Feature Set

Highlights key functionalities like plug-in heads, sampling tube compatibility, and addressability.

Contents of the Duct Smoke Detector Kit

Lists all components included in the product package for installation.

Before Installing

Provides pre-installation guidance, safety notices, and references to standards.

Limitations of Duct Smoke Detectors

Crucial safety information regarding detector usage as a substitute for life safety protection.

Detector Installation

Verify Duct Air Flow Direction and Velocity

Check air speed parameters (100-4000 FPM) before mounting the detector in the duct.

Determine Mounting Location and Configuration

Select the correct position and orientation (side-by-side or top-over-bottom) for the detector.

Drill the Mounting Holes

Instructions for creating pilot and sampling tube holes using templates.

Secure the Duct Detector to the Duct

Steps for attaching the detector housing to the ductwork using provided screws.

Sampling Tube Installation

Guidance on installing the air sampling tube, ensuring correct airflow direction.

Sampling Tube Selection

How to choose the correct sampling tube length based on duct width.

Sampling Tube Modifications

Procedures for adapting sampling tubes to non-standard duct widths by adding holes.

Remote Sampling Tube Installation

Guidelines for mounting sampling tubes separately from the detector housing.

Measurement Tests

Air Flow Verification

Testing differential pressure across sampling tubes for correct air flow (0.01-1.11 inches of water).

Low Flow Air Flow Test

Using a specific transmitter for verifying air speed in low-flow systems (under 500 FPM).

Field Wiring and System Setup

Field Wiring Guidelines

Compliance with electrical codes, wire gauges, and conductor color-coding.

Wiring Instructions

Steps for connecting the detector to the control panel via terminal strips.

Set the Address

Configuring the detector's unique address using rotary code wheel switches.

Verification of Operation

Procedures to confirm the detector is functioning correctly, checking LEDs and panel status.

Detector Cleaning Procedures

Steps for safely cleaning the detector's sensor using vacuum or compressed air.

Test and Maintenance Procedures

General Test and Maintenance

Following NFPA 72 recommendations for testing and maintenance frequency.

Test the Unit

Methods for functionally testing the detector using magnets or remote accessories.

Resetting the Detector

Procedure for resetting the detector via the system control panel after testing.

Smoke Entry Test

Using aerosol smoke to verify alarm activation and proper air flow.

Sensor Replacement and Optional Accessories

Sensor Replacement

Instructions for removing and replacing the SK-PHOTOR sensor head.

Optional Accessories

Information on compatible accessories like remote alarm LEDs and test stations.

Remote Test Using Sensor

Using a sensor with remote test capability without an accessory test coil.

Remote Test Using Test Coil

Installing an accessory coil (DCOIL) for remote test station functionality.

Additional Module Option

Accommodating relay or control modules within the detector housing.

Related product manuals