112 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
System
Options
cont
Communication
Options
Edit Ethernet
IP
Address
Section Edit
Ethernet
Subn
Mask
SubNet
Default
Gateway
DHCP
Enable
AlarmNet Timers
Ethernet Supervise
75 sec, 90
Sec, 3 min, 5
min, 1 hr, 24
hrs, 30 days,
None
*5 Minutes
Section
AlarmNet
Timers
Cellular Supervise
24Hrs, 30
days, none
*24 Hours
Old Alarm Time
10 min, 15
min, 30
Minutes, 1 hr,
2 hrs, 4 hrs, 8
hrs, 12 hrs,
24hrs, none
*30 Minutes
Phone Line Gains
Dialing
High
*High
Section Phone
Line Gains
Low
Normal
Reporting
Low
*LowNormal
High
Time Options
Water Flow Delay 0 - 90 Seconds *1 sec
Water Flow delay is the
number of seconds before a
water flow alarm is generated.
Section Water Flow Delay
Alarm Verify 60 to 250 seconds *60 sec
Alarm Verification time section
Alarm Verify
Low AC Report Time 0 - 30 hours *3 hrs
Low AC Report Delay. Section
AC Report Delay
AC Freq:
50 Hz
*60Hz
Section Change AC Line
Frequency
60 Hz
Internal
Clock Display Format
AM/PM
*AM/PM
System Clock Format (AM/PM
or military). Section Clock
Display Format (AM/PM or
Military)
MIL
Auto-resound
4 hours
*24 hours
Section Auto-Resound (4 or 24
hours)
24 hours
Menu Options/Defaults Comments
Table 8.2 Programming Quick Reference Table

Table of Contents