26 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
1. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or 240 VAC.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during
that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be
drawn from the panel.
4. Use next size battery with capacity greater than required.
EVS-50W or EVS-125W Audio Amplifier
with/without EVS-CE4
(4 max.) Standby: 10 mA mA
Alarm: 10 mA mA
EVS-INT50W Internal Amplifier (4 max.) Standby: 52 mA mA
Alarm @ 25V: 275 mA mA
Alarm @ 70V: 310 mA
mA
EVS-VCM Voice Control Module (1max.) Standby: 70 mA mA
Alarm: 100 mA mA
EVS-SW24 Switch Expander (5 max.) Standby: 10 mA mA
Alarm: 25 mA mA
EVS-LOC Remote Command Unit
(includes 6860, RVM & SW-24)
(4 max.) Standby: 100 mA mA
Alarm: 150 mA mA
EVS-100W 100W Amplifier (4 max.) Standby/Alarm: 10 mA mA mA
EVS-100WBU backup daughter card (4 max.) Standby/Alarm: 10 mA mA mA
A Total System Current
Network Cards
SK-NIC Network Interface Card (1 Max.) Standby/Alarm: 21 mA mA mA
SK-FML Fiber Optic Multi Mode (1 Max.) Standby/Alarm: 53 mA mA mA
SK-FSL Fiber Optic Single Mode (1 Max.) Standby/Alarm: 79 mA mA mA
Auxiliary Devices
3
Refer to devices manual for current rating.
IPDACT-2 IP Communicator (1 max.) Standby: 93 mA mA
Alarm: 136 mA mA
IPDACT-2UD IP Communicator (1 max.) Standby: 98 mA mA
Alarm: 155 mA mA
CELL-MOD/CELL-CAB-SK Standby: 55 mA mA
Alarm: 100 mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
B Auxiliary Devices Current
Notification Appliance Circuits Refer to device manual for current rating.
5495/5499 Power Supply 24 VDC One input circuit: 15 mA
mA
Both input circuits: 30 mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
C Notification Appliances Current
mA
D Total current ratings of all devices in system (line A + line B + C) mA mA
E Total current ratings converted to amperes (line D x .001): A A
F Number of standby hours: H
G Multiply lines E and F. Total standby AH AH
H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H
I Multiply lines E and H. Total alarm AH
AH
J Add lines G and I.
4
AH
Multiply by the Derating Factor x 1.25
Total ampere hours
required
Device # of Devices Current per Device
Standby
Current
Alarm
Current
Table 3.3 Current Draw Worksheet for SD SLC Devices