7
# ISU ISU Name ISU Options (factory default in bold)
218 Reversing Valve O/B
0 = O (O/B in Cool) 
1 = B (O/B in Heat)  
Note: This option is only displayed if the Heat Pump configured. Select 
whether reversing valve O/B should energize in cool or in heat.
220 Cool Stages / Compressor Stages 
200=Conv / 200=HP 
0, 1
Note: Select how many Cool or Compressor stages of your equipment 
the thermostat will control. Set value to 0 if you do not have Cool Stage/
Compressor Stage.
221 Heat Stages / Backup Heat Stages
1
Note: Select how many Heat or Aux/E stages of your equipment the 
thermostat will control. 
230 Fan Control in Heat 1 = Equipment Controls Fan
2 = Thermostat Controls Fan 
Note: This ISU is only displayed if ISU 205 is set to Electric Forced Air or 
Fan Coil.
300 System Changeover
0 = Manual
1 = Automatic 
Note: Thermostat can automatically control both heating and cooling to 
maintain the desired indoor temperature. To be able to select “automatic” 
system mode on thermostat home screen, turn this feature ON. Turn OFF 
if you want to control heating or cooling manually.
303 Auto Changeover Differential  0 °F to 5 °F
0.0 °C to 2.5 °C
Note: Differential is NOT deadband. Differential means how far past the 
setpoint before switching to the mode selected. Deadband setup is not an 
option. Honeywell uses an advanced algorithm that fixes deadband at 0 
°F.  This is more advanced than previous thermostats.
365 Compressor Cycle Rate (Stage 1) 1 - 6 
Note: This ISU is only displayed when Cool /Compressor Stage is set to 
1 stage. Cycle rate limits the maximum number of times the system can 
cycle in a 1 hour period measured at a 50% load. For example, when set 
to 3 CPH, at a 50% load, the most the system will cycle is 3 times per 
hour (10 minutes on, 10 minutes off). The system cycles less often when 
load conditions are less than or greater than a 50% load.
370 Heating Cycle Rate (Stage 1)  1 - 12 
Note: This ISU is only displayed when Heat Stage is set to 1 stage. Cycle 
rate limits the maximum number of times the system can cycle in a 1 
hour period measured at a 50% load. For example, when set to 3 CPH, 
at a 50% load, the most the system will cycle is 3 times per hour (10 
minutes on, 10 minutes off). The system cycles less often when load 
conditions are less than or greater than a 50% load. The recommended 
(default) cycle rate settings are below for each heating equipment type: 
Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced 
Air = 3 CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 
3 CPH; Hot Water Radiant Heat = 3 CPH; Steam = 1 CPH.
370 Heating Cycle Rate Auxiliary Heat 1 - 12 
387 Compressor Protection 0 = Off
1 - 5 minutes 
Note: The thermostat has a built in compressor protection (minimum 
off timer) that prevents the compressor from restarting too early after 
a shutdown. The minimum-off timer is activated after the compressor 
turns off. If there is a call during the minimum-off timer, the thermostat 
shows “Wait” in the display. This ISU is displayed if ISU 220 is set to at 
least 1 stage.
425 Adaptive Intelligent Recovery 0 = No
1 = Yes  
Note: Adaptive Intelligent Recovery (AIR) is a comfort setting.  Heating or 
cooling equipment will turn on earlier, ensuring the indoor temperature 
will match the setpoint at the scheduled time.
430 Minimum Cool Setpoint 50 °F to 99 °F (50 °F)
10.0 °C to 37.0 °C (10.0 °C)
Note: The cool temperature cannot be set below this level.
431 Maximum Heat Setpoint 40 °F to 90 °F (90 °F)
4.5 °C to 32.0 °C (32 °C) 
Note: The heat temperature cannot be set above this level.
Advanced setup options (ISU) (continued)