6
1 Press and hold CENTER and buttons for
approximately 3 seconds to enter advanced
menu.
2 Press Select to enter ISU.
3 Press Select to cycle through menu setup
options.
4 Press or to change values or select
from available options.
5 Press Select and confirm your settings or
press Back to ignore changes and return
to ISU menu screen to continue editing
another setup option.
6 To finish setup process and save your
setting, press Home and return to Home
screen.
NOTE: A complete list of all setup (ISU)
parameters and options starts below and
continues through page 10.
Installer setup (ISU)
Advanced setup options (ISU)
NOTE: Depending on system settings, not all options may be available.
# ISU ISU Name ISU Options (factory default in bold)
120 Scheduling Options 0 = NonProgrammable
2 = 52 Programmable
3 = 511 Programmable
4 = 7Day Programmable
Note: You can change default MOFR, SASU schedule here. To edit
periods during days, temperature setpoints, or to turn Schedule On/Off,
touch MENU and go to SCHEDULE.
125 Temperature Indication Scale
0 = Fahrenheit
1 = Celsius
200 Heating System Type
1 = Conventional Forced Air Heat
2 = Heat Pump
3 = Radiant Heat
5 = None (Cool Only)
Note: This option selects the basic system type your thermostat will
control.
205 Heating Equipment Type Conventional Forced Air Heat:
1 = Standard Efficiency Gas Forced Air
2 = High Efficiency Gas Forced Air
3 = Oil Forced Air
4 = Electric Forced Air
5 = Hot Water Fan Coil
Heat Pump:
7 = Air to Air Heat Pump
8 = Geothermal Heat Pump
Radiant Heat:
9 = Hot Water Radiant Heat
12 = Steam
Note: This option selects the equipment type your thermostat will control.
Note: This feature is NOT displayed if feature 200 is set to Cool Only.