T775P SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
11 62-0256—11
PROGRAMMING OVERVIEW
The controller must be programmed before being placed 
into service.
IMPORTANT
During programming, the controller is live at all 
times. For example, the contacts may open and 
close when adjusting the setpoint.
The programming process uses a hierarchical menu 
structure that is easy to use. You press the  and  
arrow buttons to move forward and backward through the 
menus. 
NOTES:
1. The T775P controller interface is intuitive. You 
may want to use these procedures simply as 
a reference to locate the particular option or 
parameter of interest.
2. The menus can display only those relays that 
are defined in Setup (see “1.3.1. Number of 
STAGES” on page 15). For example, if you 
configure only one relay, then only one relay 
displays on the appropriate menus.
3. If you press the HOME button or there is no 
keypad activity for four minutes, you exit Pro-
gram mode and return to the home screen.
4. If you press the MENU button, you exit 
Program mode and return to the menu.
Setpoint
The following describes the function of the setpoint for 
heating and cooling. One setpoint is programmed and is 
used by all the outputs (stages).
Heating Mode Setpoint 
In heating mode, the relay de-energizes when the 
temperature rises to the setpoint. When the temperature 
drops to the setpoint, the relay energizes.
Cooling Mode Setpoint
In cooling mode, the relay de-energizes when the 
temperature falls to the setpoint. When the temperature 
rises to the setpoint, the relay energizes.
Setpoint High Limit
You can set an irreversible setpoint high limit maximum 
value for the displayed setpoint value. 
Adjust the setpoint to the desired maximum setpoint. 
Then, simultaneously press the HOME, , and  buttons 
and continue to press all three buttons for five seconds to 
set the setpoint high limit maximum to this value.
NOTE: You must press all three buttons at exactly 
the same time for this action to occur.
IMPORTANT
1. This action sets the maximum setpoint value for 
all outputs to the setpoint high limit maximum.
2. Setting the high limit setpoint maximum is irre-
versible. If you perform the action inadvertently 
and this setpoint adversely affects the control of 
your system, you must replace the controller.
Stages (Relays) and Pump Output
The T775P model can be used to stage multiple relays 
from a singe heat or cool setpoint. The number of stages 
can be freely chosen, limited by the number of relays 
available (up to 12 relays [11 if using the pump output] 
using two T775S expansion modules).
The T775P provides a pump output using the last of the 
four SPDT relay outputs on the T775P controller. When 
T775S Expansion Modules are used, the configurable 
pump output is the last relay output of the last expansion 
module. See Table 4.
IMPORTANT
If the stage configuration is changed (e.g., the 
number of stages [relays] changes) then you 
must use Setup mode to re-select the pump 
stage. See “1. Setup” on page 12.
Staged Operation
Staging occurs as illustrated in Fig. 18 for a Heat setpoint 
of 200°F and a throttling range of 20°F when the Integral 
value is zero (0). When the Integral is not zero, then the 
actual temperatures at which stages energize and de-
energize will vary from this example; see “1.3.3.2. 
INTEGRAL” on page 17. 
NOTE: A non-zero integral causes the control to 
move toward the setpoint value.
Fig. 18. Staging Behavior 
(when effective Setpoint = 200°F).
Sensor Control
Sensor A (supply) or Sensor C (return) must always be 
the controlled temperature. In Reset applications, Sensor 
B must always be the controlling temperature (e.g. the 
Table 4. T775 Stages and Pump Output.
 Maximum
Stages
with no Pump
Output
Maximum
Stages
with Pump
Output
Relay #
Used for
Pump
Output
T775P 4 3 4
T775P & one 
T775S
878
T775P & two 
T775S
12 11 12
M24297A
THROTTLING RANGE
STAGE 2 ON
STAGE 3 ON
STAGE 1 ON
-25%
STAGES
HYST.
75%
205°F 185°F
0%
200°F
25%
195°F
STAGE 4 ON
50%
190°F
STAGE 1
STAGE 2
STAGE 3
STAGE 4
STAGE ENERGIZES STAGE DE-ENERGIZES