T775P SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0256—11 24
Fig. 57. Setup High Alarm Limit.
1.4.1.1. HIGH LIMIT
1. From the Alarms menu, use the and  buttons to 
highlight HI LIMIT.
2. Press the  button to display the high alarm limit 
temperature.
3. Use the  and  buttons to increase/decrease the 
temperature.
Default: 220°F (104°C)
Range: -10 to 248°F (-23 to 120°C)
4. Press the  button to accept the value and display 
the Alarms menu.
Fig. 58. Setup Low Alarm.
1.4.2. LOW ALARM
Only Sensor A can be used to sense the low alarm 
temperature. Sensor C cannot be used.
1. From the Alarms menu, use the  and  buttons to 
select LO ALARM.
2. Press the  button to display the alarm options.
3. Use the  and  buttons to select YES or NO.
Default: NO
4. Press the  button to accept the value and display 
the Alarms menu.
Selecting YES displays the LO LIMIT option on the 
Alarms menu once you exit this screen. Continue with 
“1.4.2.1. LO LIMIT”.
For systems with no low limit alarm, select NO, press 
the  button, and continue with “1.4.3. DIF ALARM” on 
page 25.
Fig. 59. Setup Low Alarm Limit.
1.4.2.1. LO LIMIT
1. From the Alarms menu, use the and  buttons to 
highlight LO LIMIT.
2. Press the  button to display the low alarm limit 
temperature.
3. Use the  and  buttons to increase/decrease the 
temperature.
Default: 135°F (57°C)
Range: -30 to 220°F (-34 to 104°C)
4. Press the  button to accept the value and display 
the Alarms menu.
ENABLE
ALARM
HIGH
LIMIT
SETUP
ALARMS
HI LIMIT
M24683
220
F
o 
SETUP
  ALARMS
 HI LIMIT
SETUP
ALARMS
LO ALARM
M24684
YES
NO
ENABLE
LOW
LIMIT
ALARM
SETUP
  ALARMS
 LO ALARM
ENABLE
ALARM
LOW
LIMIT
SETUP
ALARMS
LO LIMIT
M24685
135
F
o 
SETUP
  ALARMS
 LO LIMIT