VISIONPRO
®
8000 WITH REDLINK™
135 68-0312—01
ZONING
The following diagrams show the wiring for zoning with different IAQ equipment.
Fig. 346. RedLINK VisionPRO thermostats with an HZ432 zone panel and no IAQ control.
C RC RC RC R
RH
RC
W1/E
W2
W3
Y1
Y2
G
O
B
DS/BK
M34527
TRANSFORMER
RC
M1
M4
M6
R
C
W1/E
W2
W3
Y1
Y2
G
O/B
L
DATS
DATS
OT
OT
AZ1
AZ2
ZONE 4
DAMPER
THERMOSTATEQUIPMENTPOWERSENSORS ACCESSORIES
C7735A1000
DATS
A
B
C
D
THM4000R1000
WIRELESS
C
R
W
W2
Y
Y2
G
FURNACE
4
4
1
5
5 2
2
2
R
C
CON E T
POW R
THM4000R
CON E TE
W RE ESS S TUP
1
3
3
1
VISIONPRO THERMOSTATS CAN BE POWERED BY ANY TRANSFORMER. IN THIS EXAMPLE THEY ARE POWERED BY
THE SAME TRANSFORMER THAT POWERS THE HZ432.
THERE CAN BE UP TO 4 VISIONPRO THERMOSTATS USED WITH A SINGLE THM4000R WIRELESS ADAPTER AND HZ432
ZONE PANEL. THE THM4000R CANNOT BE USED IF THERE ARE MORE THAN 4 ZONES IN THE SYSTEM.
RH/RC JUMPER INSTALLED WHEN SINGLE HEAT/COOL TRANSFORMER IS USED.
DOTTED LINES APPLY ONLY TO MULTI-STAGE EQUIPMENT. SEE HZ432 INSTALLATION INSTRUCTIONS FOR
HEAT PUMP WIRING.
A THM4000R CANNOT BE USED WITH THE VISIONPRO THERMOSTAT IF THE THERMOSTAT IS CONTROLLING HUMIDIFICATION,
DEHUMIDIFICATION, OR VENTILATION.