EasyManua.ls Logo

Honeywell TH8110R1008 Vision Pro 8000 - To 12 CPH

Honeywell TH8110R1008 Vision Pro 8000
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VISIONPRO
®
8000 WITH REDLINK™
68-0312—01 32
315 Heat Cycles Per
Hour Stage 2
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type.
1 to 12 CPH
Conv. Forced
Air = 5 CPH
Heat Pump =
3 CPH
Radiant Heat =
3 CPH
Both No This ISU is only displayed when ISU 207 Heat
Stages is set to 2 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load. The
recommended cycle rate settings are below
for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
315 Heat Cycles Per
Hour Stage 3
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type.
1 to 12 CPH
Conv. Forced
Air = 5 CPH
Heat Pump =
3 CPH
Radiant Heat =
3 CPH
Both No This ISU is only displayed when ISU 207 Heat
Stages is set to 3 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load. The
recommended cycle rate settings are below
for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes

Table of Contents

Related product manuals