VISIONPRO
®
8000 WITH REDLINK™
68-0312—01 26
303 Cool Differential
Stage 2
Comfort
1.0° F to 3.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed when the
thermostat is set to 2 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling. For
example, if stage 2 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 2 turns
on. When set to Comfort, the thermostat uses
the stage of cooling as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
303 Cool Differential
Stage 3
Comfort
1.0°F - 4.0°F from setpoint (in
0.5° F increments)
Comfort Commercial No ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed when the
thermostat is set to 3 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling. For
example, if stage 3 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 3 turns
on. When set to Comfort, the thermostat uses
the stage of cooling as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
303 Cool Differential
Stage 4
Comfort
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
Comfort Commercial Yes ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed when the
thermostat is set to 4 cool stages.
The indoor temperature must rise to the
selected differential setting before the
thermostat turns on the stage of cooling. For
example, if stage 4 is set to 2° F (1.0° C), the
indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 4 turns
on. When set to Comfort, the thermostat uses
the stage of cooling as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes