VISIONPRO
®
8000 WITH REDLINK™
45 68-0312—01
610 Water Leak Alert
is [See Settings]
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects water.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects water.
611 Shutdown Alert
None
S1
S2
S3
S4
None Both Yes Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the System
Shutdown Dry Contact Device.
612 Shutdown Alert is
[See Settings]
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects a problem.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a problem.
613 Service Alert
None
S1
S2
S3
S4
None Both Yes Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the Service
Needed Dry Contact Device.
614 Service Alert is
[See Settings]
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects a problem.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a problem.
615 Fan Failure Alert
None
S1
S2
S3
S4
None Both Yes Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the Fan Failure
Dry Contact Device.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes