HPS Technical Support Page 5
11
Insert the other end of the replacement display cable (foils should be facing toward the
display board) into the display board connector and close latch.
12
Replace any boards removed in step 4.
13
Slide the retainer to the left then slide the terminal board back into place. Slide retainer to
engage the tabs and tighten the screws.
14
Attach the wires removed in step 2.
15
Close the Bezel and secure four captive screws to a torque value of .20Nm (1.5 Lb-in).
WARNING! Do not apply power until the bezel is closed.