Section 3 - Installing the Control
3-19
123456789
4142TR
CABLE
GRAY (GROUND)
YELLOW (OUT 1)
RED (OUT 2)
GREEN (GROUND)
BROWN (OUT 3)
BLUE (GROUND)
BLACK (OUT 4)
WHITE (GROUND)
J7 CONNECTOR
N/U
IF USED:
1. OUT 1 IS NO LONGER
USABLE FOR SMOKE DETECTOR RESET
(SEE FIELD 1*46).
2. OUT 2, 3, 4 CAN STILL BE
USED TO PROVIDE ALARM
STATUS INDICATIONS OR
TO OPERATE A KEYSWITCH
(SEE FIELD *15).
3. THE 675 IS NOT UL LISTED.
BROWN
GROUND START
TRIGGER
BLUE
GREEN
BLACK
VIOLET
TO AUX. POWER
TERM. 7
TO AUX. POWER
TERM. 6
(50mA CURRENT DRAW)
675
GROUND
START
MODULE
(CUT ORANGE
JUMPER)
TO
TELCO
RING
TO
EARTH
GROUND
Figure 3-24: Ground Start Module Connections
Installing a Remote Keyswitch
A UL-Listed remote keyswitch, such as the ADEMCO
4146, can be used for remote arming/disarming of the
burglary portion of the system and for silencing
alarms. The keyswitch can operate in only one
particular partition.
The keyswitch is wired across zone 7. This zone is no
longer available as a protection zone. Be sure to
program Zone 7 with a response type (e.g., type 10).
Operation
A momentary short across zone 7 arms the
partition in the AWAY mode, and a short held for
more than 10 seconds arms the partition in STAY
mode 1. A subsequent short disarms the partition.
The keyswitch LEDs indicate the partition’s status
(see table below).
A momentary short across Zone 7 silences alarm
bell and keypad sounds, and disarms the system if
it was armed. A subsequent short across Zone 7
clears the alarm memory indication and resets 2-
wire smoke and glassbreak detectors (if used).
LED Indications
Green Red Indication
On Off Disarmed & Ready
Off Off Disarmed & Not Ready
Off On Steady Armed Away
Off Slow Flash Armed Stay
Off Rapid Flash Alarm Memory
The keyswitch reports as user 0, if
Open/Close reporting is enabled in field 40.
Keyswitch Tamper Operation
The tamper switch need not be used for fire or UL
Household Burglary installations. For UL Commercial
Burglary installations, the tamper switch must be
wired to a zone (zone 6 in Figure 3-25).
Program that zone for Day Trouble/Night Alarm
(response type 5). When the keyswitch is removed
from the wall, the tamper switch opens, causing an
alarm or trouble on the zone. This also causes the
control to disable keyswitch operation until the tamper
is restored and the associated partition is disarmed.
Wiring for the Remote Keyswitch
To install the ADEMCO 4146 keyswitch, perform the
following steps:
Step Action
1 Connect the ADEMCO 4146 to the panel as
shown in Figure 3-25.
2 If you are using the tamper, make sure it is
connected to a zone.