6. Use the Battery Selection Table to select the
appropriate battery for the installation.
Table 6: Battery Selection Table
Capacity Recommended Battery Comment
4AH Yuasa NP4-12
7AH Yuasa NP7-12
12AH Yuasa NP12-12 Fits in large
mercantile
cabinet only.
14AH Yuasa NP7-12 Connect two
in parallel.
17.2AH Yuasa NPG18-12 Fits in large
mercantile
cabinet only.
7. Connect the battery, referring to Figure 3-42.
The standby battery is automatically tested for
10 minutes every 4 hours, beginning 4 hours
after exiting Programming mode. In addition,
entry into the Test mode initiates a battery
test. The VISTA-128BP/VISTA-250BP also
runs a 5-second battery test every 60 seconds
to check if the battery is connected.