EasyManua.ls Logo

Honeywell VISTA-128BP - Summary Of Audible Notification; Sound, Cause, and Display Correlation

Honeywell VISTA-128BP
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 5 – Data Field Descriptions
5-9
DO NOT cross-zone a fire zone with a burglary zone under any circumstance. Cross a fire zone with another fire
zone only, and BOTH must be protecting the same physical area (no walls or partitions separating them).
Consult NFPA 72 standard for exact spacing requirements. We recommend that spacing between fire cross-
zones be no farther than 30 ft
.
Conditions That Affect Cross-Zone Operation
If one of the zones in a pair is bypassed or has a zone response type set to 0, the cross-zoning feature does not
apply.
If an entry/exit zone is paired with an interior follower zone, be sure to enter the entry/exit zone as the first zone
of the pair. This ensures that the entry delay time is started before the follower zone is processed.
If a relay is programmed to activate on a fault of one of the zones, the relay activates without the other zone being
faulted.
If a relay is programmed to activate on either an alarm or trouble, both zones must trip before the relay will
activate, and both zones must restore for the relay to deactivate (if relay is programmed to deactivate on a Zone
List Restore).
If the one of the zones trips and the second zone does not trip within the 5-minute period, an error message is
reported to the central station. The Contact ID event code is 378.
FIELD
TITLE and DATA ENTRIES EXPLANATION
1*22
Cross Zoning Pair One
Enter 001-250
Enter 000,000 to disable
Select the first pair of cross zones, which must both be faulted within a five-
minute period to cause an alarm.
Must be 000,000 for UL installations.
1*23
Cross Zoning Pair Two
Enter 001-250
Enter 000,000 to disable
Select the second pair of cross zones, which must both be faulted within a five-
minute period to cause an alarm.
Must be 000,000 for UL installations.
1*24
Cross Zoning Pair Three
Enter 001-250
Enter 000,000 to disable
Select the third pair of cross zones, which must both be faulted within a five-
minute period to cause an alarm.
Must be 000,000 for UL installations.
1*25
Cross Zoning Pair Four
Enter 001-250
Enter 000,000 to disable
Select the fourth pair of cross zones, which must both be faulted within a five-
minute period to cause an alarm.
Must be 000,000 for UL installations.
1*26
Panic Button or Speedkey
For A, B, C keys:
00 = panic function
01-32 = macro number
For D key:
00 = to select a macro to execute when key is
pressed
01-32 = macro number
Select for the A, B, and C keys whether the system performs a panic or a
speedkey function when the key is pressed.
Select for the D key whether the system performs a specific macro or if the user
will select a macro when the key is pressed.
NOTES:
If using the A, B, and C, keys for panic alarms, verify fields *22 and *85 are
programmed correctly.
If a user code with global arm/disarm is used to execute the macro, the users
global capabilities will override any arm/disarm commands in the macro
sequence.
1*28
RF Transmitter Low Battery
Sound
0 = disarmed state only
1 = both armed and disarmed states
Select when the RF transmitter low-battery condition should display and audible
beep annunciate on the keypad.
Must be 1 for UL installations.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM

Table of Contents

Other manuals for Honeywell VISTA-128BP

Related product manuals