3 EN2R-9004 0606R20-NE
FEATURES
General
All burner control safety functions concentrated in one reli-
able and optimized system.
Specially designed to provide the optimum system solution
in gas appliances with a DBI or IP system to light the main
burner.
Both gas control and ignition control incorporate time
proven design concepts assuring reliability.
ON/OFF control of main burner by electric operator and
electric servo operator directly energized from ignition con-
trol.
Easy assembly of ignition control on gas control by plug-
ging it on from the top.
Mounting orientation may be within 90
°
in any direction
from the electric on/off operator upright position.
Gas control
Inlet 18.6 mm and outlet 18.6 mm connections are
straight through and can receive flanges.
The following closing force models are available: B + J;
B + C; B + B.
Servo pressure regulator provides stable outlet pressure.
Pressure feedback ensures constant burner pressure in
relation to combustion chamber pressure.
All adjustments are accessible from the top.
9 mm diameter pressure taps on top face for checking inlet
and outlet pressure
An internal fine mesh screen is incorporated at the inlet of
the gas control. This screen is not removable for cleaning.
An outlet screen is optional.
Two mounting holes for self tapping screws are at the bot-
tom of the gas control for rigid attachment to the appliance.
Functional options
Fast open and SOFTLITE versions
Fully adjustable
SOFTLITE option to facilitate the smooth
light-up of burner and for changing over from one gas to
another.
NOTE:
SOFTLITE opening is not always available when the
second valve is classified as a class B valve.
100 mbar inlet pressure versions available on request
Throttle valve versions
Electrical modulation (Modureg) or CVI-m.
Electrical High-Low control.
Pilot outlet for IP system
Gas/Air ratio version available.
Gas connection options
Internal thread (ISO 7-1), external thread (ISO-R228) or
flanged connections. See table 4, 5, 6 and 7, page 9.
Side outlet option for both main and pilot gas.
The side outlet for pilot and main gas can only be con-
nected to a flanged burner manifold.
Pilot gas connection for tubing with 4 mm outer diameter is
located at the outlet end of the gas control.
Pressure feedback fittings for 4 or 6 mm silicon tube can be
mounted.
End outlet or side outlet
Quick connection for Mini Venturi
Electrical connection options
The appropriate ignition control can be connected to the
valve by plugging it on.
Wired plug (IP 40) for connection with a remote ignition
control.
Rectifier plug (IP 40) for use with any standard DBI ignition
system.
24 Volt versions available for use in conjunction with other
ignition controls than S4565/S4585 series.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell vk81 series and is the answer not in the manual?

Honeywell vk81 series Specifications

General IconGeneral
BrandHoneywell
Modelvk81 series
CategoryControl Systems
LanguageEnglish

Related product manuals