Install Gas Control
1. This gas control can be mounted 0-90 degrees, in any
direction, including vertically, from the upright position of
the gas control knob.
2. Mount the gas control so gas flow is in the direction
of the arrow on the bottom of the control.
3. Thread pipe the amount shown in Table 4 for inser-
tion into the gas control. DO NOT THREAD PIPE TOO
FAR. Valve distortion or malfunction may result if the pipe
is inserted too deeply into the gas control.
TABLE 4—NPT PIPE THREAD LENGTH IN
INCHES.
Maximum Depth
Pipe Can Be
Pipe Thread Pipe Inserted Into
Size This Amount Control
3/8 9/16 3/8
1/2 3/4 1/2
3/4 13/16 3/4
4. Apply a moderate amount of good quality pipe
compound (do not use Teflon tape) to pipe only, leaving
two end threads bare. On LP installations, use compound
resistant to LP gas. Refer to Fig. 5.
5. Remove seals over gas control inlet and outlet if
necessary.
4
Fig. 5—Use moderate amount of pipe compound.
Fig. 4—Install sediment trap.
Fig. 6—Proper use of wrench on gas control with and without flanges
GAS
CONTROL
GAS
CONTROL
HORIZONTAL
DROP
PIPED
GAS
SUPPLY
PIPED
GAS
SUPPLY
3 IN.
(76 MM)
MINIMUM
3 IN.
(76 MM)
MINIMUM
RISER
GAS
CONTROL
TUBING
GAS
SUPPLY
HORIZONTAL
DROP
3 IN.
(76 MM)
MINIMUM
RISER
M3077
2
1
2
2
1
2
ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
CAUTION: SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING
END CAP TO PREVENT GAS FROM FILLING THE WORK AREA. TEST
FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.
TWO IMPERFECT
THREADS
GAS CONTROL
THREAD PIPE THE AMOUNT
SHOWN IN TABLE FOR
INSERTION INTO GAS CONTROL
APPLY A MODERATE AMOUNT OF
PIPE COMPOUND TO PIPE ONLY
(LEAVE TWO END THREADS BARE).
M3075B
PIPE
APPLY WRENCH
FROM TOP OR
BOTTOM OF GAS
CONTROL TO
EITHER SHADED AREA
WHEN FLANGE IS NOT USED
APPLY WRENCH
TO FLANGE ONLY
WHEN FLANGE IS USED
M3085A