Instructions for Use
ComPass B 4023841-001
Settings Assignment Asjustment Default Customer
setting
IE>
Relay responds to earth
faults (non-directional)
On
Off
Adjustable for
each relay
IE> A
Relay responds to earth fault
direction A
On
Off
Adjustable for
each relay
IE> B
Relay responds to earth fault
direction B
On
Off
Adjustable for
each relay
L1
Relay responds to fault only
on phase L1
On
Off
Adjustable for
each relay
L2
Relay responds to fault only
on phase L2
On
Off
Adjustable for
each relay
L3
Relay responds to fault only
on phase L3
On
Off
Adjustable for
each relay
V>
Overvoltage On
Off
Adjustable for
each relay
V<
Undervoltage On
Off
Adjustable for
each relay
Test
Relay responds to
test mode
On
Off
Adjustable for
each relay
DevErr
Relay responds to device
error
On
Off
Adjustable for
each relay
RELAY Standard conguration
Relais 1 Relay operates at:
short-circuit direction A, •
direction B,
non-directional
Common message for •
all phases L1, L2, L3
Test mode•
Type NO
Mode Momentary
I>> On
I>> A On
I>> B On
IE> Off
IE> A Off
IE> B Off
L1 On
L2 On
L3 On
V> Off
V< Off
Test On
DevErr Off
Relay 2 Relay operates at:
short-circuit direction A, •
direction B,
non-directional
Common message for •
all phases L1, L2, L3
Test mode•
Type NO
Mode Momentary
I>> Off
I>> A Off
I>> B Off
IE> On
IE> A On
IE> B On
L1 On
L2 On
L3 On
V> Off
V< Off
Test On
DevErr Off
21