EasyManua.ls Logo

Horstmann ComPass B - Fault Direction Determination

Horstmann ComPass B
29 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instructions for Use
ComPass B 4023841-001
The ComPass B works with the following response criteria:
Overcurrent detection for phase currents (I>>) and earth current (I
E
>)
Earth current and neutral point displacement voltage (I
E
> & V
NE
>) for resonant earthed/isolated
networks
Overvoltage (V>) and undervoltage (V<)
The unit allows individual settings of delay times for all of the above mentioned response criteria.
Whenever one or more of the specied response criteria are met, the ComPass B identies the na-
ture of the error and determines the direction of the fault using the sampled values of the affected
voltages and currents.
Fault direction3.1.2.
Short-circuit/earth fault in solidly earthed & low-impedance systems
As for short-circuits and earth fault in solidly earthed and low-impedance systems, the ComPass B
determines the angle between the fault current and the fault voltage of the affected phases to de-
rive the direction of a fault therefrom. If the impedance angle ranges from -45° to +135°, the Com-
Pass B determines a forward fault (↓B direction).
Earth fault in resonant earthed/isolated systems
As for earth faults in resonant earthed/isolated networks, the ComPass B uses the wattmetric me-
thod. Here the direction of a fault is determined by the phase-to-neutral voltage V
NE
and the earth
fault current I
E
.
In some cases it is not possible to determine the direction of a fault, especially when the fault is
located close to the switchgear unit the ComPass B is installed into. In such cases the ComPass B
signals an error without directional indication.
Resonant earthed network operation (cos φ)
In resonant earthed networks, the ComPass B determines the direction of the active power
of the earth fault (V
NE
x I
E
x cos φ)
The ComPass B is provided with an integrated dead zone (non-coloured area, see gure
10) for too low levels of earth fault current I
E
, or for phase angles that are unfavourably loca-
ted between V
NE
and I
E
.
Angle diagramFigure 10:
V
NE
7
Dipl.-Ing. H. Horstmann GmbH