Base unit Baseline Options
Fans 3 fan modules (fan redundancy
standard)
No additional options supported.
Additional
items
1 front USB, 2 back USB, 1 internal
USB
HP DL360 G7 Server power specifications
Specification Value
BTU 1794
Voltage 120 VAC
Plug Type NEMA 5–15P
Circuit Breaker 15 amp
Pole 1
AMP Draw 5.5
HP DL360 G7 Server environmental specifications
Specification
Value
Temperature range
Note:
All temperature ratings shown are for sea level. An altitude
derating of 1°C per 300 m (1.8° per 1,000 ft.) to 3048 m
(10,000 ft.) is applicable. No direct sunlight allowed.
Operating 10°C to 35°C (50°F to 95°F)
Shipping -40°C to 70°C (-40°F to 158°F)
Maximum wet bulb
temperature
28°C (82.4°F)
Relative humidity
(noncondensing)
Note:
Storage maximum humidity of 95% is based on a maximum
temperature of 45° C (113°F). Altitude maximum for storage
corresponds to a pressure minimum of 70 kPa.
Installing the HP ProLiant DL360 G7 Server
12 Installing the HP DL360 G7 Server November 2010