Electrical specifications
Table 5 Compute enclosure power options
Number of power
cords required (per
enclosure)
Power receptacle
requiredCircuit type
Plug or connector
type
Source voltage
(nominal)Source type
4L15-30R. 3-pole,
4-wire
30A 3-phaseNEMA L15-30p,
3-Pole, 4-wire, 3m
(10ft) power cord
200–220 VAC
line-to-line
(phase-to-phase),
3–phase
3–phase
50Hz/60Hz
4IEC 309, 4–pole,
5–wire, red
16AIEC 309, 4–pole,
5–wire, Red, 3m
(10ft) power cord
220 VAC to 240
VAC line-to-neutral
3–phase
3–phase
50Hz/60Hz
12IEC 32016A/20A
Single-phase
IEC 320
C19-C20
200V to 240V ac
50Hz/60Hz
Single-phase
C19
NOTE: When wiring a 3-phase enclosure, phase rotation is unimportant.
Table 6 Single-phase power cords
Where usedDescriptionPart number
International - otherStripped end, 240 V8120-6895
InternationalMale IEC309, 240 V8120-6897
ChinaMale GB-1002, 240 V8121-0070
North America/JapanMale NEMA L6-20, 240 V8120-6903
Table 7 Compute enclosure single-phase HP 2400 W power supply specifications
ValueSpecification
IEC-320 C19-C20Power cord
2400 W per power supplyOutput
Input requirements
200 VAC to 240 VACRated input voltage
50-60 HzRated input frequency
13.8 A at 200 VACRated input current per power supply (maximum)
13.3 A at 208 VAC
12.6 A at 220 VAC
100 A for 10 msMaximum inrush current
1.16 mAGround leakage current
0.98Power factor correction
Table 8 Compute enclosure 3-phase HP 2400 W power supply specifications (North America/Japan)
ValueSpecification
NEMA L15-30pPower cords (4)
Electrical specifications 23