Table 2. Power distribution configurations for using one to four HP BladeSystem c7000 enclosures in
a standard rack
No. of
c7000
enclosures
Input
Feed
Recommended HP
PDU with AC input plug type
No. of
PDUs
Reqd. [1]
1Ф
output
current
per PDU
Total 1Ф
output
current
available
[3]
Total output
power
available
1Ф
208VAC
Modular, 252663-D75
w/CS8265 50A non-NEMA
2 40 80 A 16.6 kW
1
1Ф
220VAC
Modular, 252663-B34
IEC309 60A 3-wire blue
2 40 80 A 17.6 kW
1Ф
208VAC
Modular, 252663-D75
w/CS8265 50A non-NEMA
4 40 160 A 33.3 kW
1Ф
220VAC
Modular, 252663-B34
IEC309 60A 3-wire blue
4 40 160 A 35.2 kW
3Ф ∆
208VAC
Monitored, AF916A
w/IEC309 60A 4-wire blue
2 84 168 A 35.0 kW
2
3Ф Y
220VAC
Monitored, AF917A
w/IEC309 32A 5-wire red
2 96 192 A 42.2 kW
1Ф
208VAC
Modular, 252663-D75
w/CS8265 50A non-NEMA
6 40 240 A 50.0 kW
1Ф
220VAC
Modular, 252663-B34
w/IEC309 60A 3-wire blue
6 40 240 A 52.8 kW
3Ф ∆
208VAC
Monitored, AF916A [2]
w/IEC309 60A 4-wire blue
2 84 168 A 35.0 kW
3Ф Y
220VAC
Monitored, AF917A [2]
w/IEC309 32A 5-wire red
2 96 192 A 42.2 kW
3
3Ф Y
220VAC
Monitored, AF917A [2]
w/IEC309 32A 5-wire red
4 96 384 A 84.5 kW
1Ф
208VAC
Modular, 252663-D75
w/CS8265 50A non-NEMA
8 40 320 A 67.0 kW
1Ф
220VAC
Modular, 252663-B34
w/IEC309 60A 3-wire blue
8 40 320 A 70.4 kW
3Ф ∆
208VAC
Monitored, AF916A [2]
w/IEC309 60A 4-wire blue
2 84 168 A 35.0 kW
4
3Ф Y
220VAC
Monitored, AF917A [2]
w/IEC309 32A 5-wire red
4 96 384 A 84.5 kW
[1] The number of required PDUs coincides with number of facility AC feeds. For PDU choices, access the online
PDU matrix through the URL provided in the “For more information” section.
[2] Configuration requires optional 600mm rack extension kit (P/N AF058A).
[3] Redundant operation requires double this amount of Total 1Ф output current.
Products and part numbers discussed in this document are subject to change without notice. For the
latest product and part numbers, access the URL provided in the “