Connecting the serial communications port
CAUTION: Use only the computer interface cable supplied with the UPS to connect the communications port to the host
computer.
NOTE: This port is only used for firmware upgrades. To update the UPS firmware, see the Hewlett Packard Enterprise
website.
Connecting the RPO port
WARNING: To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, a UPS installed in a
computer equipment room must be connected to an RPO circuit.
IMPORTANT: The remote switch must be in the O (open) position to enable power to the output receptacles.
NOTE: Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or equivalent).
Separate wire pairs are attached to a single, normally open contact in a parallel connection. Hewlett Packard Enterprise
recommends using dierent colors for the positive and negative wires.
If a connector becomes disconnected and is reconnected with reversed polarity, an RPO is initiated. To avoid RPO port
disconnect:
Minimize wire strain while connecting the RPO port.
Avoid allowing the wires to hang in the rear of the UPS.
Use tie wraps and tie wrap blocks to secure the wires tightly to the rack and the rear of the UPS.
Installation
21