EasyManua.ls Logo

Huawei RRU3832 - Installing an RRU Power Cable

Huawei RRU3832
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 9-22 Opening clips
Step 4 Remove the waterproof block.
NOTE
Remove only the waterproof blocks for the cables to be installed.
----End
9.10 Installing an RRU Power Cable
This section describes the procedure for installing an RRU power cable.
Prerequisites
l A tool-less female connector (pressfit type) is added to the RRU power cable on the RRU
side. For details, see 12.1 Adding a Tool-Less Female Connector (Pressfit Type) to the
RRU Power Cable on the RRU Side.
l A connector or OT terminals are added to the RRU power cable on the power device side.
For details, see the DBS3900 Installation Guide.
Context
If a power device provided by the customer is used, the recommended specification of the circuit
breaker on this power device is 15 A to 30 A.
There are four types of RRU power cables in terms of cross-sectional areas: 3.3 mm
2
(0.005 in.
2
) (12 AWG) and 5.3 mm
2
(0.008 in.
2
) (10 AWG) complying with North American standards,
and 4 mm
2
(0.006 in.
2
) and 6 mm
2
(0.009 in.
2
) complying with European standards.
Table 9-2 describes the RRU power cable.
RRU3832&RRU3632
Installation Guide
9 Installing RRU Cables
Issue 05 (2014-06-30) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
106

Table of Contents