PowerCube 5000
User Manual (SmartLi 100Ah)
Copyright © Huawei Technologies Co., Ltd.
Table 5-5 Settings Wizard
Select a desired language.
Set to the local time and date.
Set this parameter as required.
Set this parameter based on the number of battery
strings in the lithium battery cabinet.
Module battery LVD
voltage
If the voltage of a single battery module is lower
than the value of this parameter, the battery module
is automatically powered off. Set this parameter
based on site requirements.
To enable the EPO function, set this parameter to
Enable.
If this parameter is set to Enable, an alarm is
reported after the fire extinguishing action is
triggered.
If the MDU is directly connected to a computer,
the IP address can only be allocated manually.
The IP addresses of the MDU and network
management system must be on the same
network segment, and must be different.
If the MDU is connected to a computer through
a LAN switch or router with the DHCP
function, the IP address can be allocated
manually or automatically. Manual allocation is
used by default.
Set this parameter according to the address
information provided by the network administrator.
The IP address of the lithium battery cabinet must
be the same as the lithium battery cabinet IP
address set in the ICC cabinet.
----End
5.5 Powering On Loads
Procedure
Step 1 Turn the output disconnector of the isolation transformer to ON.
Step 2 Turn the AC output circuit breaker in the ICC cabinet to ON.
Step 3 Enable the system output.