PowerCube 5000
User Manual (SmartLi 100Ah)
B Alarm List for the Lithium Battery Cabinet
Copyright © Huawei Technologies Co., Ltd.
B Alarm List for the Lithium Battery
Cabinet
For more alarms, see the UPS5000 and SmartLi Alarm Reference.
Alarm ID
(Alarm
ID-Alarm
Cause ID)
The cell temperature is too
high.
Take measures to reduce the
ambient temperature.
The cell temperature is too
low.
Take measures to increase the
ambient temperature.
The battery voltage reaches
the high-voltage alarm
threshold.
1. Check the power cabinet
status.
2. Check the lithium battery
cabinet status.
1. The battery voltage
reaches the low-voltage
alarm threshold.
2. The input fuse is blown.
1. Check the input source
and charge batteries in a
timely manner.
2. Check whether the input
fuse is normal.
The battery charge current
reaches the overcurrent
alarm threshold.
1. Check the power cabinet
status.
2. Check the lithium battery
cabinet status.
The battery discharge
current reaches the
overcurrent alarm threshold.
1. Check whether the
power cabinet is
overloaded. Reduce the
power cabinet load to a
proper range.
2. Check the lithium battery
cabinet status.