PowerCube 5000
User Manual (SmartLi 100Ah)
A Alarm List
Copyright © Huawei Technologies Co., Ltd.
152
Device
Name
Alarm Name
Alarm
Severit
y
Fault Cause
Troubleshooting
Insufficient
Alarm Space
Warning
The number of
historical alarms is
about to reach the
upper threshold.
Export historical alarms in time.
Abnormal
System Voltage
Check
Major
The system hardware is
faulty.
Contact Huawei technical support.
Abnormal
System Current
Check
Major
The system hardware is
faulty.
Contact Huawei technical support.
Mark SC Alarm
Major
No alarms are not
reported to the Tower
Company's SC due to
manual control.
Check whether alarm masking is
configured for the SC. If not yet
configured, contact Huawei technical
support.
UIM
Temp1 Sensor
Missing
Warning
1. The Temp1 sensor
is not connected.
2. The Temp1 sensor
connector is loose.
3. The Temp1 sensor
is faulty.
1. Check whether the Temp1 sensor is
connected.
2. Check whether the temperature
sensor connector is loose.
3. Replace the faulty temperature
sensor.
Temp2 Sensor
Missing
Warning
1. The Temp2 sensor
is not connected.
2. The Temp2 sensor
connector is loose.
3. The Temp2 sensor
is faulty.
1. Check whether the Temp2 sensor is
connected.
2. Check whether the temperature
sensor connector is loose.
3. Replace the faulty temperature
sensor.
Temp1 Sensor
Fault
Major
The Temp1
temperature sensor is
faulty.
Replace the Temp1 temperature sensor
and check whether the alarm is cleared.
Temp2 Sensor
Fault
Major
The Temp2
temperature sensor is
faulty.
Replace the Temp2 temperature sensor
and check whether the alarm is cleared.
Temp1 High
Temperature
Minor
1. The ambient
temperature exceeds
the upper threshold.
2. The upper ambient
temperature alarm
threshold is
incorrectly set.
3. The temperature
sensor is faulty.
1. Check whether temperature control
devices such as the fan and air
conditioner are malfunctioning.
2. Check whether the high temperature
alarm threshold is incorrectly set.
3. Replace the faulty temperature
sensor.
Temp2 High
Temperature
Minor
1. The ambient
temperature exceeds
the upper threshold.
1. Check whether temperature control
devices such as the fan and air
conditioner are malfunctioning.