Parameter Recommended Value Description
Communication
disconnection detection
time
3 Under the Spanish
RD1699 grid standard, it
is recommended to set it
to 1S.
Fail-safe power threshold 0
Plant active power
gradient
0
Figure 3-2
Table 3-2
Parameter
Recommended Value
Active power change gradient 125%/s,If the maximum value range is
50%/s, set this parameter to 50%/s.
Soft start time 20
Soft start time after grid failure 20
Communication interrupt shutdown Enable
Communication resumed startup Enable
Communication interruption duration 1
Plant active power gradient 0
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 7