3.1.3 Step 3 Conguring Export Limitation Parameters
If the DO switch-on/o operations are not involved, ignore the switch-on/o
congurations.
Figure 3-3
Parameter Conguration
Parameter
Value Range Default Value Description
Start control Yes/No No Enable/Disable
Export Limitation
feature. Set this
parameter to Yes.
Otherwise, the
export limitation
feature does not
take
eect.
Electric meter
power direction
Positive/Reverse Reverse Set this
parameter to
Positive if the
active power
reading of the
power meter is
positive when
the inverter has
no power output.
Otherwise, set
this parameter to
Reverse.