Parameter Value Range Default Value Description
Limitation mode Total power/
Single-phase
power
Total power Total power:
Backow
prevention for
the total power
of the grid-tied
point.
Single-phase
power:
Backow
prevention for
each phase of
the grid-tied
point.
(COUNTIS
E43:Not
applicable to
Load Imbalance.)
Maximum grid
feed-in power
(0.000,
1000.000)kW
0.000kW Maximum output
power of the
inverter to the
power grid
Suggestion: Set
this parameter
according to the
threshold
allowed by the
local power
company.
Power lowering
adjustment
period
(0.2,300.0)s 0.5s Inverter output
power lowering
period. Refer to
Empirical
Parameters.
(If it is consistent
with Maximum
protection time,
the power can be
lowered for
100% in a single
step.)
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 9