Parameter Value Range Default Value Description
Maximum
protection time
(3.0,300.0)s 3.0s The maximum
duration of the
inverter output
power to the
power grid
exceeding the
preset threshold
detected by the
SmartLogger. If
Switch-o with
0% power limit
is enabled, DO
switch-o is
triggered. This
parameter is
used with Power
lowering
adjustment
period. Refer to
Empirical
Parameters.
Suggestion: Set
this parameter
according to the
maximum
duration allowed
by the local
power company.
Power raising
threshold
(0.001,
50.000)kW
5.000kW Inverter output
power raising
threshold.The
recommended
setting is
1%~2%Pn.
Fail-safe power
threshold
(0.0, 100.0)% 100.0% Inverter output
power
percentage
controlled by the
SmartLogger
when
communication
between the
SmartLogger and
the power meter
is abnormal.
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 10

Other manuals for Huawei SmartLogger3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SmartLogger3000 and is the answer not in the manual?

Huawei SmartLogger3000 Specifications

General IconGeneral
BrandHuawei
ModelSmartLogger3000
CategoryData Loggers
LanguageEnglish

Related product manuals