Parameter Value Range Default Value Description
Switch-o with
0% power limit
Enable/Disable Disable Enables or
disables DO
switch-o. The
default value is
Disable. When
enabled and the
power is limited
to 0%, the DO
performs the
corresponding
action (the hold
time is 5
seconds) if the
current reverse
ow does not
disappear after 5
seconds.
Switch-o
control port
No/DO1/DO2/D
O3
No Set the Switch-
o control port
based on actual
cable connection.
Switch-on
control port
No/DO1/DO2/D
O3
No Set the Switch-
on control port
based on actual
cable connection.
Switch-o state
feedback port
No/DI1/DI2/DI3/
DI4
No Set the Switch-
o state
feedback port
based on actual
cable connection.
Switch-on state
feedback port
No/DI1/DI2/DI3/
DI4
No Set the Switch-
on state
feedback port
based on actual
cable connection.
Empirical Parameters
Meter
Model
Power
Lowering
Adjustment
Period
Maximum
Protection Time
Description
UMG 0.5s 3s
COUNTIS
E43
0.5s 3s
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature
Issue 04 (2022-10-24) Copyright © Huawei Technologies Co., Ltd. 11

Other manuals for Huawei SmartLogger3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SmartLogger3000 and is the answer not in the manual?

Huawei SmartLogger3000 Specifications

General IconGeneral
BrandHuawei
ModelSmartLogger3000
CategoryData Loggers
LanguageEnglish

Related product manuals