Parameter Value Range Default Value Description
Limitation mode Total power/
Single-phase
power
Total power Total power:
Backow
prevention for the
total power of the
grid-tied point.
Single-phase
power:
Backow
prevention for
each phase of the
grid-tied point.
(COUNTIS
E43:Not
applicable to Load
Imbalance.)
Maximum grid
feed-in power
(0.000,
1000.000)kW
0.000kW Maximum output
power of the
inverter to the
power grid
Suggestion: Set
this parameter
according to the
threshold allowed
by the local power
company.
Power lowering
adjustment period
(0.2,300.0)s 0.5s Inverter output
power lowering
period. Refer to
Empirical
Parameters.
(If it is consistent
with Maximum
protection time,
the power can be
lowered for 100%
in a single step.)
SmartLogger3000
Export Limitation Conguration Guide 3 Conguting Export Limitation Feature