EasyManuals Logo

Huawei SMU01C User Manual

Huawei SMU01C
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
SMU01C
User Manual
A LCD menu
Issue 03 (2015-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
43
Main Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Default Value
Range
DC Under Volt
≤ FC Volt – 2
V)
BLVD Enable
-
Yes
Yes, No
BLVD
-
43.0V
38.0 V44.9 V
(38.0 V ≤
BLVD Volt
LLVD Volt)
LLVD Enable
-
No
Yes, No
LLVD
-
44.0V
BLVD Volt to
DC Under Volt
AC Settings
Over Volt
-
280VAC
181 V AC300
V AC
(> AC Under
Volt)
Under Volt
-
180VAC
60 V AC279 V
AC
(< AC Over
Volt)
Alarm Settings
Alarm Severity
Alarm Name
Level
-
Alarm Name
Level: Minor,
Major
Digital Alarm
Digital No
1
1, 2
Mode
High
High, Low
Relay Relate
Alarm
Mains Fault
-
Relate Relay
None
None, ALM1,
ALM2, ALM3,
ALM4
Default Type
NO
NC, NO
Rect Settings
Sleep Enable
-
No
Yes, No
Best Effi Point
-
70%
60%-80%
Exch Cycle
-
7days
5 days-30 days
Min Num Rect
On
-
1pcs
1 pcs5 pcs
Load HT Off
LHTD Enable
-
No
Yes, No
Load Off Temp
-
70°C
50°C 80°C
Rect Off Time
-
240Min
1255 Min