Huawei UPS5000-E-200K-SM - User Manual

Huawei UPS5000-E-200K-SM
300 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power
Modules)
Issue
02
Date
2017-02-25
HUAWEI TECHNOLOGIES CO., LTD.

Table of Contents

Other manuals for Huawei UPS5000-E-200K-SM

Questions and Answers

  • M
    mkruegerAug 10, 2025
    What to do if the Huawei Control Unit inverter is not normal?
    • J
      Jason ThompsonAug 11, 2025
      If your Huawei Control Unit inverter isn't working normally, it might be due to an overload or a short circuit. Try reducing the load or fixing any short circuits. Alternatively, the power module could be faulty, in which case you should replace it.
  • T
    Terry SkinnerAug 17, 2025
    Why does my Huawei Control Unit UPS work in bypass mode and not transfer to inverter mode?
    • G
      goodmanshannonAug 17, 2025
      If the Huawei Control Unit UPS is stuck in bypass mode and won't switch to inverter mode, the working mode might be incorrectly set; ensure it's set correctly. Also, if the bypass transfer times have reached their limit, clear the faults on the LCD.
  • R
    Robert RodriguezAug 22, 2025
    What to do if the Huawei Control Unit charger generates an alarm?
    • M
      moralesdavidAug 22, 2025
      If the Huawei Control Unit charger generates an alarm, it could be due to several reasons. The charger itself might be failing, or it could be experiencing overcurrent or undervoltage. In the case of charger failure or overcurrent, replace the power module. If it's undervoltage, check if the configured number of batteries is correct. If it is correct and the alarm persists, replace the power module.
  • T
    teresagarrettAug 28, 2025
    What to do if the Huawei Control Unit bypass is not normal?
    • R
      ramosheatherAug 28, 2025
      If the Huawei Control Unit bypass is not working normally, it could be due to a damaged bypass thyristor, which requires replacing the bypass module. Another reason could be the bypass module experiencing overtemperature. In this case, reduce the load or improve ventilation.
  • C
    carpentertravisSep 4, 2025
    Why is the Huawei Control Unit rectifier not working, and the bus voltage is not boosted?
    • A
      Anthony BarkerSep 4, 2025
      If the rectifier of your Huawei Control Unit isn't working and the bus voltage isn't being boosted, it might be because the mains voltage is too high (above 280 V) or too low (below 80 V). Check the mains voltage against these thresholds, and if it's outside this range, contact the electric power company.

Huawei UPS5000-E-200K-SM Specifications

General IconGeneral
ModelUPS5000-E-200K-SM
Power Capacity200 kVA
Phase3-phase
Frequency50/60 Hz
Efficiency≥ 96%
Relative Humidity0% to 95% (non-condensing)
Cooling MethodForced air cooling
Protection LevelIP20
Input Voltage380/400/415 V
Output Voltage380/400/415 V
Battery TypeLithium-ion / Lead-acid
Battery Voltage384 V
Communication PortsRS485, USB
Operating Temperature0°C to 40°C
Noise Level<65 dB
Capacity200 kVA / 200 kW