UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
119
Figure 3-85 Cable connections for a dual-bus system
(1) Mains input power
cables
(2) Bypass input power
cables
(3) Battery
cables
(4) Output power
cables
----End
3.3.3 Connecting Signal Cables
Context
A maximum of four UPS5000-E-200K-SM/FMs and UPS5000-E-300K-SM/SMTs can be
connected in parallel. Cable connection principles for two UPSs connected in parallel are the
same as those for four UPSs connected in parallel. The following describes how to connect
cables for four UPSs connected in parallel.
Procedure
Step 1 Connect the parallel ports on the UPSs using parallel cables.
Figure 3-86 shows the topology diagram for the N+X parallel system and Figure 3-87
shows the cable connections for this system.